Description
REX521GHHPSH50G Product Introduction
Overview
The REX521GHHPSH50G is a multifunctional medium-voltage feeder protection relay manufactured by ABB, belonging to the legacy REX521 series. It integrates protection, measurement, circuit breaker control, supervision and event logging for distribution feeders, large MV motors and backup transformer protection in industrial and utility power systems. This relay accepts inputs from conventional CT and VT, supports multiple neutral earthing schemes, and is widely stocked as surplus/refurbished spare for outage replacement and lifecycle extension of existing MV switchgear. ABB ceased active production of the REX521 platform in 2012ABB Group.

Key Features & Benefits
- Comprehensive ANSI protection suite: multi-stage non-directional / directional overcurrent, earth fault, thermal overload, phase unbalance, overvoltage, undervoltage, over/under frequency and residual overvoltage protectioneero
- Built-in auto-reclose function, configurable for up to 5 reclose shots, ideal for overhead distribution feeders
- Circuit breaker control, trip circuit supervision and CB failure protection logic
- High-precision metering of current, voltage, power, power factor and harmonic monitoring for power quality supervision
- Local 2×16 character LCD HMI with keypad for parameter setting, real-time values, alarm viewing and fault records
- Time-stamped event recorder and fault waveform capture for post-trip root cause analysis
- Multiple serial communication options for SCADA and DCS integration; compatible with ABB relay setting software
- Configurable digital inputs, trip outputs and signal contact outputs for interlocking and alarm annunciation
- Rugged panel-mount design, suitable for indoor switchgear cabinets in power plants, refineries and substations
- Multi-processor DSP architecture for fast, deterministic protection response
Technical Specifications
| Item | Description |
|---|---|
| Manufacturer | ABB |
| Model | REX521GHHPSH50G |
| Type | MV Feeder / Motor Protection Relay, REX521 Series |
| CT Input | 1 A / 5 A secondary CT compatible |
| VT Input | 100 V rated voltage transformer input |
| Auxiliary Supply | Wide-range AC/DC auxiliary power (PSH variant) |
| Protection Functions | 50/51, 67, 50N/51N, 67N, 46, 49F, 27, 59, 81U/O, auto-reclose 79 |
| I/O | 9 digital inputs, multiple trip / signal output relays |
| HMI | 2×16 LCD display + navigation keypad |
| Communication | Serial protocol for remote SCADA connection |
| Rated Frequency | 50 / 60 Hz software selectable |
| Mounting | Panel cutout mounting for MV switchgear |
| Operating Temperature | -40°C ~ +70°C |
| OEM Status | Discontinued; available as surplus / refurbished spare |
| Application | Distribution feeders, MV motor feeders, transformer backup protection, substation single busbar schemes |
Typical Applications
REX521GHHPSH50G is deployed on medium voltage switchgear in power generation auxiliary systems, refineries, chemical plants and utility substations. Common uses include incoming/outgoing feeder protection, large fan/pump MV motor protection and backup protection for distribution transformers. It is a critical spare for planned outages and maintenance of legacy ABB protection panels; ABB’s recommended modern replacement platform is the Relion 615 series relay familyABB Group.
Matching Companion Items
- ABB REX521 PC setting software
- Current transformers, voltage transformers
- Relion 615 series as retrofit upgrade solution
Operation Notes
Verify CT/VT ratios, auxiliary supply voltage and protection setting coordination before commissioning. All protection curves, earth-fault direction logic and auto-reclose sequences must be validated against the single-line diagram. Back up relay configuration files before replacement. The ordering suffix defines hardware I/O and communication variant; direct swap is only permitted with matching part code and firmware revision.
FAQ
Q: Can REX521GHHPSH50G replace the GE SR469 motor relay you listed earlier? A: Not directly. SR469 is optimized for dedicated motor thermal protection with advanced RTD thermal modelling, while REX521 is primarily a feeder relay with general motor protection capability. Setting logic and thermal algorithms differ substantially.
Q: Can it interface with Emerson DeltaV DCS? A: Yes via serial protocol mapping, but it is not a native DeltaV module. Separate serial gateway or controller serial card is required.
Q: What is the recommended modern replacement? A: ABB Relion 615 series feeder protection relays, with dedicated retrofit mounting kits available for drop-in panel replacementABB Group