Description
IS200STCIH4A Product Introduction
Overview
The IS200STCIH4A is a Discrete Input Terminal Board (STCI) for GE Speedtronic Mark VI / Mark VIe turbine control systems. It is the field termination interface for contact digital input signals, routing hardwired status signals from field devices to the matching Mark VI I/O pack via ribbon cable. It is widely stocked as new original, surplus or refurbished spare for gas & steam turbine control cabinet maintenance and outage replacement.

IS200STCIH4A
Key Features & Benefits
- 24 channels of optically isolated discrete digital input terminals
- Designed for 24 VDC contact input signals, surge suppression and EMI filtering on each channel
- Screw terminal block for convenient field wiring, 37-pin D-sub connector to mate with the I/O pack
- Provides electrical isolation between field wiring and the turbine control backplane to reduce ground loop risk
- Onboard signal conditioning circuit for stable contact status detection
- Conformal-coated PCB, built to adapt to high vibration, high-temperature turbine cabinet environments
- Supports TMR triple redundant architecture for safety-critical turbine protection logic
- Used for equipment status feedback, limit switches, relay contacts and permissive interlock signals
Technical Specifications
| Item | Description |
|---|---|
| Manufacturer | GE / Baker Hughes |
| Model | IS200STCIH4A |
| Type | STCI Discrete Input Terminal Board |
| Compatible System | Speedtronic Mark VI, Mark VIe Turbine Control |
| Input Rating | 24 VDC dry contact input |
| Input Channels | 24 isolated DI channels |
| Threshold | ON ≥19 VDC, OFF ≤5 VDC |
| Interface | Screw terminals + 37-pin D-Sub to I/O pack |
| Operating Temperature | -30°C ~ +65°C |
| OEM Status | Discontinued, available as surplus / refurbished spare |
| Application | Gas turbine, steam turbine generator control & protection |
Typical Applications
IS200STCIH4A collects field contact signals in combined-cycle power plant turbine control panels, including breaker status, valve limit switches, lube oil permissives, emergency stop contact feedback and auxiliary equipment alarms. It works with Mark VI I/O packs to feed status points into the turbine control and protection logic. It is a standard high-demand spare for planned outages and cabinet retrofit.
Matching Companion Modules
- Mark VI I/O Pack (DI pack)
- IS200STCI series other terminal variants (STCIH2A / STCIH6A)
- Speedtronic Mark VI controller rack, VME backplane
- Turbine HMI and ToolboxST configuration software
Operation Notes
Hardware revision and firmware compatibility with the paired I/O pack must be confirmed before replacement. After swap, verify each channel’s dry-contact status and check for noise-induced false triggers. This board is part of the safety-related turbine permissive circuit; proper functional test is mandatory after replacement.
FAQ
Q: What is the difference between IS200STCIH4A and IS200STCIH6A? A: STCIH4A is for 24 VDC input; STCIH6A is the 125 VDC version; they are not drop-in interchangeable.
Q: Can it work with Honeywell Experion or DeltaV DCS? A: No. It is proprietary Mark VI turbine hardware and cannot be used on DCS racks.
Q: Is it a standalone I/O card? A: No, it is only a termination board; it must connect to a matching Mark VI digital input I/O pack.