Honeywell CC-TAIX01 Non-Redundant Analog Input IOTA, Experion PKS Series C, 16-Channel Non-HART Termination Assembly

CC-TAIX01
Technical Specifications
- Catalog Number: CC-TAIX01 (P/N: 51308363-175)
- Brand: Honeywell Process Solutions
- Product Type: Analog Input IOTA (Input Output Termination Assembly), Non‑HART, Non‑Redundant
- Compatible IOM: CC-PAIH02 16-channel analog input module
- Channel Count: 16 analog input channels
- Supported Signals: 4–20 mA 2-wire transmitters, 1–5 VDC, 0–5 VDC
- Input Impedance: High impedance for voltage inputs
- Field Wiring: Accepts up to 14 AWG stranded wire; dual terminal blocks TB1 / TB2 for signal and return wiring
- Power: Backplane-powered via Series C I/O rack
- Operating Temperature: 0 °C ~ +60 °C (32 °F ~ 140 °F)
- Humidity: 5% to 95% RH, non‑condensing
- Construction: Conformal coated PCB for corrosive cabinet environments
- Certification: Suitable for Class I Div 2 / Zone 2 non-incendive hazardous locations
- Form Factor: Standard Honeywell Series C rack mount IOTA footprint
- Protection: Individual channel short-circuit protection; fault containment per channel
- Architecture: Non-redundant termination base
Key Features & Advantages
- 16-channel non-HART analog termination: Optimized for conventional 4–20 mA and voltage transmitters within Experion PKS Series C DCS system.
- Channel-isolated short-circuit protection: Field short on one channel will not disrupt adjacent measurement channels or the paired IOM module.
- Proven two-wire transmitter compatibility: First 12 channels support direct 2-wire transmitter connection without jumper modification; channels 13–16 configurable for alternate signal types via IOTA jumpers.
- Conformal coating: Resists moisture, dust and airborne chemical contaminants in plant control cabinets.
- Dedicated terminal blocks for simple field wiring: Clear signal and return terminals reduce wiring errors during commissioning.
- Hazardous area suitability: Approved for Division 2 / Zone 2 installations in oil, gas and chemical facilities.
- Cost-effective non-redundant design: Ideal for non-critical monitoring loops to optimize cabinet budget versus redundant CC-TAIX11.
- Tight integration with Experion PKS ecosystem: Matches Honeywell Series C I/O rack and CC-PAIH02 IOM for seamless system configuration and diagnostics.
Application Fields
- Petrochemical and refinery process monitoring (pressure, flow, level, temperature)
- Power generation boiler and auxiliary system DCS cabinets
- Chemical batch and continuous process plants
- Water and wastewater treatment control systems
- Pharmaceutical process monitoring
- Offshore platform non-safety analog measurement loops
- General manufacturing plant analog signal acquisition for Experion PKS
Related Product Recommendations
- CC-TAIX11: Redundant Analog Input Non-HART IOTA (direct redundant counterpart)
- CC-PAIH02: 16-Ch HART Analog Input IOM (the matching input module for CC-TAIX01 / CC-TAIX11)
- CC-TAID01: Non-Redundant Analog Input HART IOTA
- CC-TAID11: Redundant Analog Input HART IOTA
- CC-TAON01: Analog Output IOTA
- CC-TAOX01: Non-Redundant Analog Output IOTA
- CC-TDIL01: Digital Input IOTA
- CC-TDOL01: Digital Output IOTA
- CC-PAOX01: Analog Output IOM
- CC-TAIM01: Multiplexer IOTA for remote field termination
Installation & Maintenance
Installation
- Install CC-TAIX01 into the Honeywell Series C I/O rack, aligned with the paired CC-PAIH02 IOM. Confirm proper locking engagement to maintain backplane contact.
- Separate analog field cables from high-voltage AC and motor wiring to minimize EMI interference. Use shielded twisted pair for all analog signals; terminate shield at cabinet ground bar only.
- Torque terminal screws to the specified value to avoid loose connections under vibration.
- Configure jumpers on TB2 for channels 13–16 if connecting voltage sources or non-standard transmitters.
- Verify field loop integrity and absence of shorts before applying rack power.
- Follow site hazardous location documentation for Zone 2 / Div 2 installation control requirements.
Maintenance
- Inspect terminal block tightness and cable condition during scheduled shutdowns.
- Utilize built-in channel diagnostic status in Experion Station to identify open loop, short circuit or transmitter fault.
- Check for dust buildup and corrosion on the conformal-coated PCB; clean cabinet air filters regularly.
- If a channel short occurs, isolate the field instrument first before replacing wiring or transmitter.
- Maintain spare CC-TAIX01 assemblies for critical cabinet spares pool; avoid hot removal of IOTA while the paired IOM is active unless procedure permits.
- Record all loop calibration, wiring changes and IOTA replacement for asset and change management logs.