Honeywell CC-TAIX01 Non-Redundant Analog Input IOTA, Experion PKS Series C, 16-Channel Non-HART Termination Assembly

  1. CC-TAIX11: Redundant Analog Input Non-HART IOTA (direct redundant counterpart)
  2. CC-PAIH02: 16-Ch HART Analog Input IOM (the matching input module for CC-TAIX01 / CC-TAIX11)
  3. CC-TAID01: Non-Redundant Analog Input HART IOTA
  4. CC-TAID11: Redundant Analog Input HART IOTA
  5. CC-TAON01: Analog Output IOTA
  6. CC-TAOX01: Non-Redundant Analog Output IOTA
  7. CC-TDIL01: Digital Input IOTA
  8. CC-TDOL01: Digital Output IOTA
  9. CC-PAOX01: Analog Output IOM
  10. CC-TAIM01: Multiplexer IOTA for remote field termination
Category: SKU: Honeywell CC-TAIX01 Brand:

Description

Honeywell CC-TAIX01 Non-Redundant Analog Input IOTA, Experion PKS Series C, 16-Channel Non-HART Termination Assembly

CC-TAIX01

Technical Specifications

  • Catalog Number: CC-TAIX01 (P/N: 51308363-175)
  • Brand: Honeywell Process Solutions
  • Product Type: Analog Input IOTA (Input Output Termination Assembly), Non‑HART, Non‑Redundant
  • Compatible IOM: CC-PAIH02 16-channel analog input module
  • Channel Count: 16 analog input channels
  • Supported Signals: 4–20 mA 2-wire transmitters, 1–5 VDC, 0–5 VDC
  • Input Impedance: High impedance for voltage inputs
  • Field Wiring: Accepts up to 14 AWG stranded wire; dual terminal blocks TB1 / TB2 for signal and return wiring
  • Power: Backplane-powered via Series C I/O rack
  • Operating Temperature: 0 °C ~ +60 °C (32 °F ~ 140 °F)
  • Humidity: 5% to 95% RH, non‑condensing
  • Construction: Conformal coated PCB for corrosive cabinet environments
  • Certification: Suitable for Class I Div 2 / Zone 2 non-incendive hazardous locations
  • Form Factor: Standard Honeywell Series C rack mount IOTA footprint
  • Protection: Individual channel short-circuit protection; fault containment per channel
  • Architecture: Non-redundant termination base

 

Key Features & Advantages

  • 16-channel non-HART analog termination: Optimized for conventional 4–20 mA and voltage transmitters within Experion PKS Series C DCS system.
  • Channel-isolated short-circuit protection: Field short on one channel will not disrupt adjacent measurement channels or the paired IOM module.
  • Proven two-wire transmitter compatibility: First 12 channels support direct 2-wire transmitter connection without jumper modification; channels 13–16 configurable for alternate signal types via IOTA jumpers.
  • Conformal coating: Resists moisture, dust and airborne chemical contaminants in plant control cabinets.
  • Dedicated terminal blocks for simple field wiring: Clear signal and return terminals reduce wiring errors during commissioning.
  • Hazardous area suitability: Approved for Division 2 / Zone 2 installations in oil, gas and chemical facilities.
  • Cost-effective non-redundant design: Ideal for non-critical monitoring loops to optimize cabinet budget versus redundant CC-TAIX11.
  • Tight integration with Experion PKS ecosystem: Matches Honeywell Series C I/O rack and CC-PAIH02 IOM for seamless system configuration and diagnostics.

 

Application Fields

  • Petrochemical and refinery process monitoring (pressure, flow, level, temperature)
  • Power generation boiler and auxiliary system DCS cabinets
  • Chemical batch and continuous process plants
  • Water and wastewater treatment control systems
  • Pharmaceutical process monitoring
  • Offshore platform non-safety analog measurement loops
  • General manufacturing plant analog signal acquisition for Experion PKS

 

Related Product Recommendations

  1. CC-TAIX11: Redundant Analog Input Non-HART IOTA (direct redundant counterpart)
  2. CC-PAIH02: 16-Ch HART Analog Input IOM (the matching input module for CC-TAIX01 / CC-TAIX11)
  3. CC-TAID01: Non-Redundant Analog Input HART IOTA
  4. CC-TAID11: Redundant Analog Input HART IOTA
  5. CC-TAON01: Analog Output IOTA
  6. CC-TAOX01: Non-Redundant Analog Output IOTA
  7. CC-TDIL01: Digital Input IOTA
  8. CC-TDOL01: Digital Output IOTA
  9. CC-PAOX01: Analog Output IOM
  10. CC-TAIM01: Multiplexer IOTA for remote field termination

 

Installation & Maintenance

Installation

  • Install CC-TAIX01 into the Honeywell Series C I/O rack, aligned with the paired CC-PAIH02 IOM. Confirm proper locking engagement to maintain backplane contact.
  • Separate analog field cables from high-voltage AC and motor wiring to minimize EMI interference. Use shielded twisted pair for all analog signals; terminate shield at cabinet ground bar only.
  • Torque terminal screws to the specified value to avoid loose connections under vibration.
  • Configure jumpers on TB2 for channels 13–16 if connecting voltage sources or non-standard transmitters.
  • Verify field loop integrity and absence of shorts before applying rack power.
  • Follow site hazardous location documentation for Zone 2 / Div 2 installation control requirements.

Maintenance

  • Inspect terminal block tightness and cable condition during scheduled shutdowns.
  • Utilize built-in channel diagnostic status in Experion Station to identify open loop, short circuit or transmitter fault.
  • Check for dust buildup and corrosion on the conformal-coated PCB; clean cabinet air filters regularly.
  • If a channel short occurs, isolate the field instrument first before replacing wiring or transmitter.
  • Maintain spare CC-TAIX01 assemblies for critical cabinet spares pool; avoid hot removal of IOTA while the paired IOM is active unless procedure permits.
  • Record all loop calibration, wiring changes and IOTA replacement for asset and change management logs.