GE Multilin SR489-P5-LO-A20-E Generator management relay

Typical Applications

  • Synchronous generator protection in industrial power plants
  • Induction generator protection in cogeneration systems
  • Backup generator and standby genset protection
  • Hydro, gas turbine and steam turbine generator applications
  • Generator metering, thermal monitoring and vibration monitoring
  • Retrofit and lifecycle replacement for GE SR 489 relay systems
Category: SKU: GE SR489-P5-LO-A20-E Brand:

Description

GE Multilin SR489-P5-LO-A20-E

Brand / Model: GE Multilin SR489-P5-LO-A20-E
Product Type: Generator management relay for synchronous and induction generators

SR489-P5-LOA20-E

Product Description

The SR489-P5-LO-A20-E is a generator management relay from the GE Multilin SR 489 series. It provides protection, metering, control and monitoring for small- to medium-sized synchronous or induction generators operating at 25, 50 or 60 Hz.68

The order code indicates: P5 = 5 A phase CT secondaries; LO = low-voltage control power; A20 = 4–20 mA analog outputs; E = enhanced display.25 The relay supports draw-out construction for easier maintenance and can be configured locally or through EnerVista software.68

 

Technical Specifications

Item Description
Manufacturer GE Multilin / GE Vernova
Series SR 489 Generator Management Relay
CT Input 5 A phase CT secondaries (P5)
Control Power 20–60 VDC; 48–62 VAC at 20–48 Hz (LO)
Analog Outputs 4 × isolated 4–20 mA
Analog Inputs 4 × isolated 4–20 mA
RTD Inputs 12 RTD inputs for stator/bearing temperature monitoring
Digital Inputs 7 assignable digital inputs
Output Relays 6 programmable output relays
Communication 2 × RS485; Modbus RTU / DNP 3.0; up to 19,200 bps
Display Enhanced 40-character LCD with keypad and status LEDs
Frequency Range 0.00–90.00 Hz; operates at 25/50/60 Hz
Dimensions 21.6 × 22.4 × 25.2 cm
Weight Approx. 10 kg

Some interface and environmental ratings depend on hardware revision and firmware version. For commissioning, always verify against the relay nameplate and official GE Multilin SR 489 documentation.

 

Key Features and Advantages

  • Comprehensive generator protection: Includes stator differential, 100% stator ground, loss of excitation, reverse power, overexcitation, negative-sequence overcurrent and distance backup.68
  • Thermal and vibration monitoring: Supports RTD-based stator and bearing temperature monitoring, plus analog vibration/speed inputs.68
  • Enhanced local HMI: The E-option display provides a larger LCD for real-time metering, diagnostics and setpoint access.27
  • Flexible communication: Dual RS485 ports support Modbus RTU and DNP 3.0 for integration with SCADA, DCS or plant monitoring systems.15
  • Draw-out construction: Allows removal and replacement with minimized downtime during maintenance.68
  • Programmable logic: Built-in logic functions support custom control sequences and automation tasks.9
  • Event recording and diagnostics: Supports IRIG-B time-synchronized event records, waveform capture and data logging for fault analysis.68

 

Typical Applications

  • Synchronous generator protection in industrial power plants
  • Induction generator protection in cogeneration systems
  • Backup generator and standby genset protection
  • Hydro, gas turbine and steam turbine generator applications
  • Generator metering, thermal monitoring and vibration monitoring
  • Retrofit and lifecycle replacement for GE SR 489 relay systems

 

Related Products

  • SR489-P5-HI-A20-E: Same relay family with high-voltage control power option.
  • SR489-P1-LO-A20-E: Variant with 1 A phase CT secondaries.
  • GE Multilin G30: Advanced generator protection relay for larger or more complex applications.
  • GE Multilin SR 469: Motor management relay in the same SR series.
  • EnerVista 489 software: Configuration, monitoring and diagnostics tool for SR 489 relays.