Description
Fireye 85UVF1-1QD Phoenix II Integrated Ultraviolet Flame Scanner
Brand: Fireye (a division of Carrier Global, USA origin)
Product Line: Phoenix II Series Industrial Burner Flame Detection Family
Part Number Aliases: 85UVF1-1QD, Fireye 85UVF1-1QD UV Flame Detector, Fireye Integrated Flame Scanner Unit

85UVF1-1QD
Core Technical Specifications
| Parameter | Verified Specification |
|---|---|
| Manufacturer | Fireye (Carrier Global, USA) |
| Product Type | Phoenix II Integrated Ultraviolet Flame Scanner with Built-in Amplifier |
| System Compatibility | Fireye burner management systems, PLC/DCS industrial control platforms |
| Detection Spectrum | 190–260 nm UV wavelength (standard), 215–350 nm extended flicker detection |
| Flame Detection Response Time | < 1 second |
| Flame Failure Recognition Time | < 3 seconds |
| Analog Output | 4–20 mA current loop, proportional to flame intensity |
| Power Supply | 24 VDC nominal, 18–32 VDC wide operating range |
| Maximum Current Draw | 200 mA |
| Electrical Interface | 8-pin circular quick-disconnect (QD) connector, compatible with 59-546-XX series cables |
| Environmental Rating | NEMA 4 (IP66 equivalent) weatherproof enclosure |
| Operating Ambient Temperature | -40 °C to +65 °C |
| Internal Component Operating Temperature | -40 °C to +82 °C |
| Storage Temperature | -40 °C to +85 °C |
| Humidity Rating | 0–95% RH, non-condensing |
| Physical Dimensions | 263 × 58 × 28 mm (basic QD housing) |
| Net Weight | 2.69 kg (5.90 lbs) |
| Standard Warranty | 12 months |
Main Features and Advantages
- Fully Integrated Design: Built-in UV amplifier and flame relay eliminate the need for external signal conditioners, drastically reducing wiring complexity and potential failure points.
- High Anti-Interference Performance: 4–20 mA noise-resistant current loop output supports long cable runs in electrically noisy industrial environments.
- Automatic Calibration Function: On-board microprocessor automatically learns flame amplitude, adapts gain, and calibrates fire/no-fire thresholds to block natural light and furnace heat radiation interference.
- NEMA 4 Weatherproof Housing: IP66 equivalent dust and water splash protection ensures reliable operation in outdoor boiler houses, turbine enclosures, and process heater sites.
- Ultra-Wide Operating Temperature Range: -40 °C to +65 °C ambient temperature rating suits extreme cold and high-temperature industrial field conditions.
- Quick-Disconnect Electrical Interface: 8-pin circular QD connector enables fast on-site installation and maintenance without complex wiring operations.
Application Scenarios
- Flame detection unit for industrial boiler, process heater, and gas turbine burner management systems
- Petrochemical refinery, power plant, and offshore platform combustion equipment flame safety monitoring
- Steel mill, cement plant, and waste incineration plant industrial furnace flame status feedback
- Legacy Fireye Phoenix series flame scanner retrofit, preventive maintenance, and spare part replacement projects
- Industrial automation systems requiring high-reliability UV flame detection for critical combustion safety applications
Related Model Recommendations
- 59-546-XX: Fireye dedicated 8-pin quick-disconnect shielded cable that natively pairs with 85UVF1-1QD for field wiring.
- 85UVF1-3KD: Fireye Phoenix II extended temperature flame scanner variant for >65 °C high-temperature furnace site requirements.
- EP110: Fireye standalone burner management controller for complete combustion safety system setup.
- 85UVF1-1QD-RevA: Earlier hardware revision of 85UVF1-1QD, fully electrically compatible for direct drop-in replacement.
Related News & FAQ
- Q1: What is the typical market price range? A: Authorized global distributors list pricing from USD 350–1200, depending on unit condition, stock quantity, and regional supply chain availability.
- Q2: Is this part still in active production? A: Fireye has not issued an official end-of-life notice; new original, surplus, and refurbished units remain widely stocked across global industrial automation suppliers.
- Q3: What is the flame failure recognition time? A: It recognizes flame loss within less than 3 seconds for fast safety interlock response.
- Q4: What is the standard delivery lead time? A: Most distributors with in-stock inventory can ship via international courier (DHL/FedEx) within 3–7 working days.
- Q5: Does it require an external amplifier? A: No, it integrates the UV amplifier and flame relay internally, no extra external signal conditioner is needed.