Vibro-Meter (Meggitt) VM600 RLC16 16-Channel SPDT Relay Expansion Card

  • ‌IRC4‌: Vibro-Meter 4-channel high-power relay card variant for heavy-load safety interlock requirements.
  • ‌MPC4‌: Vibro-Meter 4-channel machinery protection processing card that natively maps alarm conditions to RLC16 relay outputs.
  • ‌ABE056‌: Vibro-Meter 16-slot large system rack for housing multiple RLC16 modules for large-scale multi-point alarm systems.
  • ‌RLC16 Mk2‌: Later hardware revision of with improved contact life, fully electrically compatible for direct drop-in replacement.
Category: SKU: Vibro-Meter-SEALED Brand:

Description

Vibro-Meter (Meggitt) VM600 RLC16 16-Channel SPDT Relay Expansion Card
‌Brand‌: Vibro-Meter (Meggitt PLC, Switzerland origin)
‌Product Line‌: VM600 Series Turbine & Rotating Machinery Protection System Family
‌Part Number Aliases‌: VM600 RLC16, DS 268-081, Vibro-Meter 16-Channel Relay Output Unit, VM600 RLC16 Alarm Relay Card

VM600 RLC16

Core Technical Specifications

Parameter Verified Specification
Manufacturer Vibro-Meter (Meggitt PLC, Switzerland)
Product Type 16-Channel Independent SPDT Relay Expansion Card
System Compatibility VM600 ABE04x/ABE056 racks, MPC4, IOC4T, CPUM modules
Number of Relay Outputs 16 fully independent SPDT relays
Relay Contact Rating 250 VAC / 30 VDC, 5 A maximum per channel
Operating Mode Selection Jumper selectable: normally energized (fail-safe) / normally de-energized
Electrical Connection 3 × screw terminal blocks (J1, J2, J3) for all field wiring
Installation Method Mounts at the rear of VM600 rack, connects directly to system backplane
Operating Temperature Range -25 °C to +65 °C
Storage Temperature Range -40 °C to +85 °C
Operating Humidity 0–90% RH, non-condensing
Storage Humidity 0–95% RH, non-condensing
Certifications CE, EAC (Eurasian Customs Union) industrial compliance
Hot-Swap Support Fully supported, no system shutdown required for replacement
Standard Warranty 12 months

 

Main Features and Advantages

  • ‌ System Native Seamless Integration‌: Purpose-built as the dedicated relay expansion module for machinery protection platforms, no extra signal conversion hardware required for direct backplane interconnection.
  • ‌16 Independent SPDT Relay Design‌: 16 fully isolated single-pole double-throw relays eliminate the need for external interposing relays, drastically reducing control cabinet wiring complexity and safety circuit failure points.
  • ‌Dual Safety Logic Configuration‌: Supports both software mapping via MPS configuration software and hardware jumper setting, enabling flexible fail-safe (normally energized) or non-trip-on-power-loss operation modes.
  • ‌Wide Harsh Environment Adaptability‌: -25 °C to +65 °C wide operating temperature range suits extreme cold industrial site and unheated turbine room conditions.
  • ‌Screw Terminal Field Wiring‌: All 16 relay channels connect via 3 dedicated screw terminal blocks, making on-site wiring, maintenance and troubleshooting far more convenient.
  • ‌Hot-Swap Maintainability‌: Supports live module replacement without system shutdown, drastically maximizing critical rotating equipment continuous monitoring uptime.

 

Application Scenarios

  • High-density alarm relay expansion unit for turbine and rotating machinery protection system deployments
  • Power plant steam/gas turbine, generator, and large pump multi-condition alarm and safety interlock output
  • Petrochemical refinery, offshore platform, and pipeline compressor fleet SIL-rated machinery protection system relay expansion
  • Steel mill, mining, and heavy industrial large rotating equipment multi-point fault alarm signal distribution
  • Legacy system retrofit, preventive maintenance, and spare part replacement projects
  • Industrial automation systems requiring high-reliability 16-channel isolated relay output for critical rotating asset safety interlock applications

 

Related Model Recommendations

  • ‌IRC4‌: Vibro-Meter 4-channel high-power relay card variant for heavy-load safety interlock requirements.
  • ‌MPC4‌: Vibro-Meter 4-channel machinery protection processing card that natively maps alarm conditions to RLC16 relay outputs.
  • ‌ABE056‌: Vibro-Meter 16-slot large system rack for housing multiple RLC16 modules for large-scale multi-point alarm systems.
  • ‌RLC16 Mk2‌: Later hardware revision of with improved contact life, fully electrically compatible for direct drop-in replacement.

 

Related News & FAQ

  • ‌Q1: What is the typical market price range?‌ A: Authorized global distributors list pricing from ‌USD 800–5000‌, depending on unit condition, stock quantity, and regional supply chain availability.
  • ‌Q2: Is this part still in active production?‌ A: Meggitt has not issued an official end-of-life notice; new original, surplus, and refurbished units remain widely stocked across global industrial automation suppliers.
  • ‌Q3: What is the maximum relay contact rating?‌ A: Each independent SPDT relay supports up to 250 VAC / 30 VDC, 5 A maximum load.
  • ‌Q4: What is the standard delivery lead time?‌ A: Most distributors with in-stock inventory can ship via international courier (DHL/FedEx) within 3–7 working days.
  • ‌Q5: Does it support fail-safe operation mode?‌ A: Yes, it supports jumper-selectable normally energized mode, where loss of power automatically triggers the relay trip action.