Description

TRICONEX 8105 Spare Board | Industrial Control System Automation Spare Part

 

Product Brief Introduction

The TRICONEX 8105 is an essential rack assembly / backplane spare board designed for the classic Tricon TMR safety instrumented system. It serves as the core interconnection carrier for processor modules, I/O modules and power supplies inside the chassis, transmitting high-speed safety bus signals between all redundant channels. Adhering to Triconex proven triple modular redundant design philosophy, this backplane board provides stable, reliable electrical connections for 2oo3 voting safety loops. It is widely used in ESD, F&G and BMS safety systems of oil & gas, petrochemical, chemical and power plants, supporting hot-swap maintenance of matched modules and guaranteeing the integrity of the safety bus.

TRICONEX 8105

Key Technical Specifications

  • Brand: TRICONEX
  • Part Number: 8105
  • Product Type: Chassis Backplane Board
  • Architecture: TMR triple redundant bus interface
  • Safety Level: SIL 3 applicable (matched with complete Tricon system)
  • Hot Swap Compatible: Yes (for plug-in modules on this backplane)
  • Operating Temperature: 0 °C ~ +60 °C
  • Storage Temperature: -40 °C ~ +85 °C
  • Relative Humidity: 5% ~ 95%, non-condensing
  • Bus: Proprietary Tricon safety backplane bus
  • EMC Standard: IEC 61000 series
  • Installation: Installed inside standard Tricon rack
  • Connector: Gold-plated high-reliability edge connectors
  • Diagnostic: Supports system bus fault detection via TriStation software
  • Material: Industrial-grade PCB, anti-corrosion, anti-aging

 

Quality Control Procedure

  1. Visual Inspection: Examine PCB surface, traces, soldering points and connectors for scratches, oxidation, cracks or missing pins.
  2. Connector Continuity Test: Check all signal and power pins for continuity and short-circuit risk.
  3. Bus Signal Integrity Test: Verify impedance and signal transmission quality of the safety bus circuit.
  4. Compatibility Verification: Confirm matching with corresponding Tricon rack and module series.
  5. Powered Burn-in Screening: Long-duration energized aging to eliminate early latent defects.
  6. Interference Simulation Test: Conduct EMC anti-interference test under industrial noise conditions.
  7. Serial Number Recording & Data Archiving: Log SN, test result and tester information for traceability.
  8. ESD Protection Packaging: Seal in anti-static shielding bag with shockproof foam before shipment.

 

Frequently Asked Questions (FAQ)

Q1: What is the function of TRICONEX 8105?A1: It is a Tricon rack backplane board, responsible for connecting processor, I/O and power modules and transferring redundant safety bus signals.

Q2: Can I replace the 8105 backplane online while the system is running?A2: No. The backplane itself cannot be hot swapped. Rack power must be cut off before replacement. Strict safety lockout-tagout (LOTO) procedure is required.

Q3: Which Tricon racks does 8105 fit?A3: It matches the classic Tricon chassis series. Please confirm your rack model and hardware revision before ordering.

Q4: What will happen if the 8105 backplane is faulty?A4: It may cause bus communication failure, module offline, frequent fault alarms or even safety system trip.

Q5: Is the backplane ESD sensitive?A5: Yes. ESD wrist strap and anti-static mat are mandatory during handling and installation.

Q6: What is the standard warranty?A6: 12 months warranty after delivery. Extended warranty service is available upon request.

 

Installation & Configuration Guide

  1. Pre-Installation Preparation
  • Execute LOTO lockout-tagout, fully cut off rack power supply.
  • Prepare ESD wrist strap, insulated screwdriver, maintenance work permit.
  • Inspect new 8105 board for physical damage and confirm part number correctness.
  1. Dismantle the Rack & Remove Old Backplane
  • Take out all modules (CPU, I/O, power supply) from the rack and put them into ESD bags one by one.
  • Disassemble rack housing and fixing screws of the faulty 8105 backplane.
  • Carefully detach wiring harnesses and grounding terminals connected to the backplane.
  1. Mount the New 8105 Backplane
  • Wear ESD protection all the time.
  • Fix the new backplane to the rack with screws; keep it flat without mechanical stress.
  • Reconnect grounding terminals and internal harnesses according to wiring drawings.
  1. Reinstall Modules
  • Insert processor, power supply and I/O modules back into original slots in order.
  • Make sure each module connector is fully engaged and front latches are locked.
  1. Power On and Commissioning
  • Double-check all wiring and short-circuit risk before power restoration.
  • Energize redundant power supplies step by step.
  • Observe module LED indicators; connect TriStation software to scan hardware.
  • Confirm all modules are detected normally and no bus fault alarm exists.
  • Perform loop test and fault simulation to validate TMR voting function.
  1. Post-Install Handover
  • Clear fault history, record backplane SN, replacement date and test data in maintenance log.
  • Restore system to standby/online state and inform operation team.

Important Reminder: Backplane replacement belongs to high-risk safety work. Never power on the rack before full inspection.

 

Related TRICONEX Models & Part Number Recommendations (15 pcs)

  1. TRICONEX 8101 Backplane
  2. TRICONEX 8102 Backplane
  3. TRICONEX 8103 Backplane
  4. TRICONEX 8104 Backplane
  5. TRICONEX 8112 Spare Board
  6. TRICONEX 8111 Power Board
  7. TRICONEX 3008 Main Processor
  8. TRICONEX 3009 Main Processor
  9. TRICONEX 3604E Digital Output Module
  10. TRICONEX 3625 Digital Input Module
  11. TRICONEX 3700A Analog Input Module
  12. TRICONEX 3703E Analog Output Module