IS220PPROH1A, GE Mark VIe PPRO Independent Backup Turbine Protection I/O Pack (Backup Overspeed & E-Stop Protection)

Model Order Number Description
PPRO Trip Terminal Board IS200TREAH2A TREA termination board for PPRO
Mark VIe Main Controller IS220UCSAH1A Mark VIe CPU
IONet Ethernet Switch IS420ESWBH2A Mark VIe IONet switch
Safety Vibration Pack IS220YVIBS1A SIL vibration protection pack
Non-safety Vibration Pack IS220PVIBH1A PVIB vibration monitor
Rack Power Supply IS200PSAH1A Mark VIe 24VDC power
Speed Probe 330104-00-05-10-02-00 Eddy current speed pickup
Speed Probe Extension Cable 330730-080-00-00 Probe extension cable
IONet Patch Cable GE-CAB-IONET IONet Ethernet cable
PPRO 37-pin Trip Cable GE-CAB-PPRO-TREA PPRO to TREA cable
Mark VIe Backplane IS200CHS02A I/O rack backplane
Analog Input Pack IS210AEAAH1B 4-20mA AI pack
Digital Input Pack IS210AEDAH1B DI I/O pack
Digital Output Pack IS210AEDBH1B DO I/O pack
ToolboxST Software TOOLBOXST-LIC Mark VIe configuration & diagnostic software
Category: SKU: IS220PPROH1A, PPRO Brand:

Description

IS220PPROH1A, GE Mark VIe PPRO Independent Backup Turbine Protection I/O Pack (Backup Overspeed & E-Stop Protection)

 

Core Product Introduction

The IS220PPROH1A (PPRO pack) is a safety-critical independent backup protection I/O pack for GE Vernova Mark VIe Speedtronic turbine control system. It provides hardware-based backup overspeed protection, emergency stop (E-Stop) monitoring, control watchdog, generator synchronization check and trip relay outputs, working independently from the main controller protection logic. It receives speed signals from magnetic pickups and emergency trip contact signals, drives turbine trip hardware via TREA / TREG trip terminal boards. Widely used on gas turbines, steam turbines, combined cycle and compressor packages; supports simplex and TMR safety architectures, supplied mainly as spare part for existing Mark VIe fleets.

IS220PPROH1A

Main Technical Specifications

Item Parameter
Part Number IS220PPROH1A
Manufacturer GE Vernova (GE Gas Power)
Platform Mark VIe Speedtronic
Function Backup overspeed, E-Stop, watchdog, sync check, turbine trip output
Speed Inputs 3 independent speed pickup channels
Communication Dual 10/100 Mbps IONet Ethernet
Termination Mate TREA / TREG trip terminal board
Safety Function Hardware overspeed trip, wire-break detection for E-stop loops
Supply Voltage 24 VDC from Mark VIe backplane
Hot Swap Supported
Operating Temperature -30 °C ~ +65 °C
Storage Temperature -40 °C ~ +85 °C
Humidity 5%–95% RH, non-condensing
Mounting Mark VIe I/O pack backplane slot mount
Weight ~0.38 kg
Certifications cULus, CE, suitable for TMR turbine protection
Lifecycle Status Obsolete, spare stock available

 

Quality Control Procedure

  1. Visual & Label Inspection: Verify original GE marking, IS220PPROH1A serial number, dual Ethernet ports, gold edge fingers; no pin damage, burn marks or PCB corrosion.
  2. Backplane Power Boot Test: Install on Mark VIe test backplane, apply 24VDC, confirm PWR, RUN, ESTP, OSPD, WDOG LED status, no abnormal heating.
  3. IONet Communication Test: Establish IONet connection, confirm ToolboxST can read module identity, revision and fault status.
  4. Speed Channel Simulation Test: Inject frequency signal to 3 speed inputs, verify overspeed threshold detection.
  5. E-Stop Loop & Wire-break Test: Simulate E-stop contact open/short circuit, validate wire-break diagnostic alarm.
  6. Trip Relay Output Test: Check Form-C trip relay action under overspeed and E-stop conditions.
  7. Watchdog function test: Simulate main controller loss, verify watchdog trip action.
  8. TREA terminal compatibility check: Confirm cable pinout matching with TREA trip board.
  9. Firmware Compatibility Check: Confirm firmware matches site ControlST / ToolboxST baseline.
  10. Packaging & Traceability: Anti-static packaging, foam protection, serial-number QC report before shipment.

 

Frequently Asked Questions (FAQ)

Q1: What is the difference between PPRO (IS220PPROH1A) and the main controller overspeed protection?A1: PPRO is independent hardware backup protection. It runs separate overspeed logic, not dependent on the main Mark VIe CPU; it provides the second layer of overspeed and emergency trip for turbine safety.

Q2: What terminal board does IS220PPROH1A pair with?A2: It connects to TREA / TREG trip termination boards via 37-pin DC cable.

Q3: Can it be hot swapped online?A3: Hot-swap hardware supported, but protection function is lost during replacement. MOC, trip bypass and alarm suppression are mandatory before swap.

Q4: Is it SIL rated?A4: It is used in turbine TMR protection architectures, but it is a dedicated backup overspeed pack, different from SIL-certified YVIB vibration safety packs. Confirm site safety requirement before substitution.

Q5: Can it work with legacy Mark VI (non-Vie)?A5: No, exclusive to Mark VIe IONet architecture; Mark VI uses separate overspeed hardware.

Q6: What does OSPD, ESTP, WDOG LED stand for?A6: OSPD = Overspeed trip status; ESTP = Emergency Stop active; WDOG = Controller watchdog fault.

 

Installation & Configuration Guide

  1. Pre-install Preparation: Mark VIe backplane, TREA trip terminal board, speed probe cables, E-stop wiring, 24VDC rack power, ToolboxST software, site MOC & trip bypass procedure.
  2. Rack Preparation: Bypass turbine trip protection and suppress related alarms per plant safety procedure.
  3. Module Insertion: Insert into designated PPRO slot and lock.
  4. Field Wiring: Connect speed pickups and E-stop chains to TREA terminals; route low-level speed cables separately from high-power cables.
  5. Power Up: Energize rack power, check RUN, LINK LEDs normal, no active trip alarms.
  6. Online Connection: Connect ToolboxST to Mark VIe controller and go online.
  7. Hardware Scan: Run chassis scan, confirm PPRO pack is detected without hardware fault.
  8. Protection Parameter Configuration: Set overspeed trip threshold, E-stop wire-break detection, watchdog timeout.
  9. Function Validation: Test speed reading, E-stop trigger, watchdog trip and relay output action.
  10. Backup: Save ControlST database, PPRO firmware and trip settings to plant archive.

Warning: This pack is part of turbine overspeed & emergency trip protection. Improper replacement or bypass may result in unplanned turbine trip or loss of safety protection.

 

Related Mark VIe Models & Accessories (15 pcs)

Model Order Number Description
PPRO Trip Terminal Board IS200TREAH2A TREA termination board for PPRO
Mark VIe Main Controller IS220UCSAH1A Mark VIe CPU
IONet Ethernet Switch IS420ESWBH2A Mark VIe IONet switch
Safety Vibration Pack IS220YVIBS1A SIL vibration protection pack
Non-safety Vibration Pack IS220PVIBH1A PVIB vibration monitor
Rack Power Supply IS200PSAH1A Mark VIe 24VDC power
Speed Probe 330104-00-05-10-02-00 Eddy current speed pickup
Speed Probe Extension Cable 330730-080-00-00 Probe extension cable
IONet Patch Cable GE-CAB-IONET IONet Ethernet cable
PPRO 37-pin Trip Cable GE-CAB-PPRO-TREA PPRO to TREA cable
Mark VIe Backplane IS200CHS02A I/O rack backplane
Analog Input Pack IS210AEAAH1B 4-20mA AI pack
Digital Input Pack IS210AEDAH1B DI I/O pack
Digital Output Pack IS210AEDBH1B DO I/O pack
ToolboxST Software TOOLBOXST-LIC Mark VIe configuration & diagnostic software