Description
Bently Nevada 3500/33 Relay Output Module, Industrial Automation Spare Part
Product Core Overview
The 3500/33 is a 16-channel relay module designed for the Bently Nevada 3500 machinery protection TSI rack system. It receives alarm and trip signals from other monitor modules inside the rack and provides dry contact relay outputs for external interlock, annunciator, PLC or ESD systems. Each relay can be independently mapped to Alert, Danger, OK or user-defined logic points. It supports programmable fail-safe operation, widely used on turbines, compressors and other rotating equipment in power, petrochemical and refining industries.This module participates in trip logic output. Improper replacement may affect machine interlock protection. The 3500/33 series is end-of-life, supplied as original surplus or fully tested refurbished spare parts for existing 3500 racks.

3500/33
Main Technical Specifications
| Item | Specification |
|---|---|
| Brand | Bently Nevada (Baker Hughes) |
| Model | 3500/33 |
| Typical Part No. | 149986-01 |
| Series | 3500 Machinery Protection System |
| Product Type | 16‑Channel Relay Output Module |
| Relay Type | Form C dry contact (NO / NC / Common) |
| Contact Rating | 5A @ 120 VAC, 5A @ 24 VDC resistive load |
| Quantity | 16 independent relays |
| Operating Mode | Fail‑safe configurable |
| Communication | Backplane bus communication with rack controller / TDI |
| Power Consumption | Approx. 7.5 W |
| Operating Temperature | -30 ℃ ~ +65 ℃ |
| Ambient Humidity | 5%–90% RH, non-condensing |
| Protection Rating | IP20, rack cabinet internal use |
| Mounting | Standard slot of 3500 rack backplane |
| Diagnostic | Module OK, fault and channel status LEDs |
| Certification | ATEX / IECEx Zone 2, UL, CSA |
| Application | Turbine, compressor, pump, fan alarm output, trip interlock, annunciator |
Quality Control Procedure
- Visual Incoming Inspection: Check front panel terminal block, rack edge connector, label, serial number and PCB condition.
- ESD Controlled Handling: All inspection and testing performed on grounded anti-static workstation with ESD wrist strap.
- Power-on Burn-in Test: Install into compatible 3500 rack, energise continuously for 4 hours; monitor LED status and temperature.
- Backplane Communication Test: Verify handshake and signal mapping with 3500/22M TDI and monitor cards.
- Relay Functional Test: Trigger mapped alarm conditions one by one, verify pull-in/release action of each relay and continuity.
- Logic Configuration Test: Confirm fail-safe setting matches specification.
- Firmware Compatibility Check: Confirm firmware revision matches the existing rack configuration.
- Data Archiving: Record serial number and full test report, attach inspection sticker, vacuum anti-static packaging.
- Pre-shipment Audit: Double-check model and contact variant before dispatch.
Recommended Related Models & Order Codes (15pcs)
- 3500/22M TDI
- 3500/15 Power Supply
- 3500/40M Proximitor Monitor
- 3500/42M Seismic / Proximitor Monitor
- 3500/45M Temperature Monitor
- 3500/50M Tachometer
- 3500/53M Relay Module
- 3500/60M Overspeed
- 3500/62M Overspeed
- 3500/92 Gateway
- 3500/94 Display
- 330104 Probe
- 330780 Extension Cable
- 3500/05 Rack
- 3500/32 I/O Module
Frequently Asked Questions
Q1: Can 3500/33 replace 3500/53M directly?A: No. 3500/33 is 16-channel general relay module; 3500/53M is a dedicated 4-channel high-integrity trip relay module for critical protection. They cannot substitute each other casually. Confirm trip logic and safety requirements.
Q2: Is this module discontinued?A: Yes, Bently Nevada 3500/33 is end-of-production. Available stock is original surplus or fully tested refurbished spare parts.
Q3: Does 3500/33 support hot swap?A: Hardware supports hot swap. But all relays on this module will lose control output during replacement, which will affect related alarm and trip interlock. Safety bypass and work permit are mandatory before replacement.
Q4: Relay output abnormal after installation, what should I check?A: Check rack backplane contact, module configuration, relay mapping table, fail-safe setting, terminal wiring and external load. Use 3500 configuration software to read logic diagnostics.
Q5: Warranty terms?A: Original surplus new: 12-month warranty. Refurbished tested stock: 6-month warranty. Damage caused by overload, short circuit on relay terminals, ESD, misconfiguration or incompatible firmware is excluded.
Q6: Commissioning software?A: Bently Nevada 3500 Rack Configuration Software and System 1. Back up relay mapping and fail-safe logic before replacement.
Installation & Configuration Guide
Pre-installation Preparation
- Confirm cabinet environment: clean, low dust, no condensation, separated from high EMI and high-voltage cabling.
- Prepare ESD protection, insulated screwdriver, multimeter, terminal wiring drawing and rack project backup.
- Complete safety permit and interlock bypass procedure for rotating equipment.
Installation Steps
- Follow site LOTO and rotating equipment safety procedure, implement interlock bypass.
- Release the module latch, pull out the faulty 3500/33 vertically from the rack slot.
- Unpack new spare under ESD protection; avoid touching backplane gold fingers.
- Insert the new module smoothly into the rack slot and lock the latch.
- Reconnect field wiring on the front terminal block strictly according to drawing.
- Verify rack protective earth connection.
Configuration & Commissioning
- Observe front panel LED status after insertion.
- Launch 3500 configuration software and connect to the rack via TDI.
- Refresh hardware tree, confirm 3500/33 is recognised online.
- Restore relay mapping, alarm assignment and fail-safe parameters from backup.
- Simulate Alert / Danger status to test each relay action and dry-contact output.
- Clear all rack alarms after self-diagnosis passes.
- Remove bypass step by step, restore interlock logic and save commissioning log.
Maintenance Notes
- Relay contacts have limited electrical life; avoid frequent switching under heavy load.
- Do not exceed rated contact current; overloading will burn relay contacts.
- Keep terminal block tight and clean to prevent poor contact.
- Store spare modules in dry sealed anti-static packaging.