Description
ABB PDP800, Symphony Plus SD Series PROFIBUS DP Master Communication Module (PDP800A: Conformal coated version)
Core Product Introduction
The PDP800 is a PROFIBUS DP master interface module for ABB Ability Symphony Plus SD series DCS platform. It connects HPC800 / SPC700 controllers to PROFIBUS DP field networks, integrating S800 remote I/O, smart transmitters, actuators, MCC, drives and IEDs. It supports both module redundancy and PROFIBUS bus line redundancy, works with electrical RS485 or fiber PROFIBUS media. It is widely used in power plants, water treatment and process industries; PDP800A is the coated variant for corrosive / offshore environments.

PDP800
Main Technical Specifications
| Item | Parameter |
|---|---|
| Part Number | PDP800 (PDP800A = conformal coating) |
| Manufacturer | ABB |
| Platform | Symphony Plus SD Series |
| Function | PROFIBUS DP V0 / V1 / V2 Master |
| Max Slaves | 125 nodes per segment |
| Baud Rate | Up to 12 Mbps |
| Media | RS485 copper or fiber optic PROFIBUS |
| Fiber Max Distance | 15 km |
| Time Stamp | 1 ms high precision timestamp (DP V2) |
| Redundancy | Master redundancy + DP line redundancy supported |
| Backplane Bus | HN800 SD backplane |
| Mounting Base | PTU810 (base for redundant pair) |
| Supply Voltage | 24 VDC |
| Operating Temperature | 0 °C ~ +60 °C (PDP800A wider harsh range) |
| Storage Temperature | -40 °C ~ +85 °C |
| Humidity | 5%–95% RH, non-condensing |
| Hot Swap | Supported |
| Certifications | CE, cULus |
| Lifecycle Status | Active, available for new project & spare |
| Weight | ~0.7 kg |
Quality Control Procedure
- Visual & Label Inspection: Verify original ABB marking, PDP800 / PDP800A part number, serial number, PROFIBUS DB9 port, HN800 backplane connector; no pin damage or corrosion.
- 24VDC Power Boot Test: Mount on PTU810 base, apply 24VDC, confirm power LED and self-test, no abnormal heating.
- HN800 Backplane Communication Test: Connect to SD test rack, verify handshake with HPC800 controller.
- PROFIBUS DP Master Test: Build DP subnet, scan slave devices, confirm device identification.
- Redundancy Switchover Test (if redundant pair): Simulate master failure, verify seamless switchover to standby PDP800.
- Fiber DP Media Test: Test fiber PROFIBUS converter link, check long-distance communication stability.
- DP V2 Timestamp Function Test: Verify 1ms event time stamping from S800 I/O.
- Fault Alarm Simulation: Simulate bus short, slave loss, cable break, check diagnostic alarm reporting.
- Firmware Compatibility Check: Confirm firmware matches Symphony Plus Composer / S+ Engineering baseline.
- Packaging & Traceability: Anti-static packaging, foam protection, serial-number QC report before shipment.
Frequently Asked Questions (FAQ)
Q1: What is the difference between PDP800 and PDP800A?A1: has conformal coating for high humidity, dust, offshore and corrosive plant environments; electrical and functional performance are identical.
Q2: What base do I need for redundant installation?A1: PTU810 mounting base, which accepts two modules for redundant master configuration.
Q3: Can it support PROFIBUS PA?A3: It does not directly connect PA devices. It works with external DP/PA coupler/link device to access PROFIBUS PA instruments.
Q4: What software configures ?A4: ABB S+ Engineering / Composer for Symphony Plus, including DTM device integration for PROFIBUS slaves.
Q5: Is it compatible with old Harmony / Melody racks?A5: No, it belongs to SD series, only works with HN800 SD backplane and HPC800/SPC700 controllers.
Q6: Can it be hot swapped online?A6: Hot-swap supported. Replacement will interrupt PROFIBUS field bus communication; MOC, alarm suppression and bypass are mandatory.
Installation & Configuration Guide
- Pre-install Preparation: PTU810 base, SD HN800 backplane, 24VDC power, PROFIBUS copper/fiber cable, S+ Composer engineering station.
- Module Installation: Snap onto PTU810 base; single or redundant pair according to design.
- Backplane & Power Wiring: Connect HN800 backplane and 24VDC supply, protective earth.
- PROFIBUS Field Wiring: Terminate bus with correct end resistor; separate DP field cable from high-voltage power cables.
- Power Up: Energize rack power, check module RUN / FAULT / DP bus LEDs.
- Online via Composer: Go online to Symphony Plus controller, scan communication modules.
- PROFIBUS Network Configuration: Create DP subnet, import slave GSD files, assign slave addresses and process data mapping.
- Redundancy Setup (if required): Enable master redundancy and line redundancy parameters.
- Signal Verification: Check real-time data from S800 I/O, transmitters and drives; test event timestamp.
- Backup: Save Composer project, GSD library and module firmware version to plant archive.
Warning: PROFIBUS bus failure will cause loss of all slave I/O. Redundant configuration is strongly recommended for critical control loops.
Related Symphony Plus SD Series Models & Accessories (15 pcs)
| Model | Order Number | Description |
|---|---|---|
| Conformal coated | with protective coating | |
| Redundant mounting base | PTU810 | Base for two modules |
| Main SD Controller | HPC800 | Symphony Plus large controller |
| Mid-range SD Controller | SPC700 | Compact Symphony Plus controller |
| S800 AI Module | AI810 | 4-20mA analog input slave |
| S800 AO Module | AO810 | Analog output slave |
| S800 DI Module | DI810 | Digital input |
| DO Module | DO810 | Digital output |
| IEC61850 Interface | CI850K01 | SD series IEC61850 comm module |
| Backplane | TU890 | SD series backplane |
| DP/PA Link Device | LD800 | PROFIBUS DP to PA coupler |
| PROFIBUS Fiber Converter | OLM/G12 | Siemens optical link module |
| SD Power Supply | SD821 | 24VDC rack power supply |
| PROFIBUS DB9 Cable | ABB-CAB-DP02 | DP bus jumper cable |
| S+ Engineering Software | SPLUS-COMPOSER | Symphony Plus configuration tool |