Overview

The 1756-PAR2 is an Allen‑Bradley (Rockwell Automation) ControlLogix AC redundant power supply assembly kit. It is used for high-availability ControlLogix PLC racks, supplying stable multi-rail backplane power for CPU, communication and I/O modules. It achieves bumpless automatic failover; one unit fails while the other continues powering the chassis without interruption. The complete kit includes two 1756-PA75R power modules, two 1756-CPR2 redundant cables and one 1756-PSCA2 chassis adapter.

1756-PAR2

Key Features & Benefits

  • Input: 85–265 VAC wide-range AC, 47–63 Hz, 75W per power unit
  • Multi-rail output: 1.2 VDC / 3.3 VDC / 5.1 VDC / 24 VDC for ControlLogix backplane
  • True hot redundancy, seamless switchover upon power module fault
  • Each power module supports hot-swap for online maintenance
  • LED status indication for power good, fault and redundancy health
  • Built-in surge suppression, overvoltage, overcurrent and short-circuit protection
  • Suitable for critical applications requiring uninterrupted control: power auxiliary, refining, chemical process
  • UL, CE, cULus certified

 

Technical Specifications

 

Item Description
Manufacturer Allen‑Bradley / Rockwell Automation
Model 1756-PAR2
Type Redundant AC Power Supply Assembly
Input 85–265 VAC, 47–63 Hz
Single Unit Power Rating 75 W
Output Rails 1.2VDC@1.5A; 3.3VDC@4A; 5.1VDC@13A; 24VDC@2.8A
Kit Contents 2×1756-PA75R, 2×1756-CPR2, 1×1756-PSCA2
Compatible Chassis Standard 1756-A4 / A7 / A10 / A13 / A17 (NOT K-keyed AxxK chassis)
Operating Temperature 0°C ~ +60°C
OEM Status Active
Application High-availability ControlLogix racks for process and power auxiliary control

 

Typical Applications

1756-PAR2 is deployed on critical ControlLogix racks paired with CPU like 1756-L73 and 1756-L75K you listed before. It is widely used for boiler/turbine auxiliary control, motor sequence control and safety interlock racks in power plants and refineries. It eliminates single-point power failure risk and serves as a key outage spare.

 

Matching Companion Items

  • Standard ControlLogix chassis 1756-A7 / A10
  • 1756-L73 / 1756-L75 Logix CPU
  • 1756 I/O modules and communication modules
  • 1756-PAR2XT (extended temperature conformal coated variant)
  • 1756-PDR2 (24VDC input redundant power kit)

 

Operation Notes

1756-PAR2 is for standard B-series chassis, it cannot be used on K-series AxxK chassis. Confirm adapter and cable version before replacement. After installation, test redundant failover function and alarm indication.

1756-PAR2K is the K-chassis redundant power counterpart, and 1756-PAR2XT is the wide-temperature coated version.

 

FAQ

Q: What is the difference between 1756-PAR2 and 1756-PAR2K? A: for standard chassis; PAR2K is for K-keyed chassis, not interchangeable. Q: Can I use only one power module from the kit? A: Yes, but redundancy function will be lost; full kit is required for redundant operation. Q: Can it supply power to Honeywell Experion or DeltaV racks? A: No, it is dedicated ControlLogix backplane power assembly.