Description
1756-PAR2 Product Introduction
Overview
The 1756-PAR2 is an Allen‑Bradley (Rockwell Automation) ControlLogix AC redundant power supply assembly kit. It is used for high-availability ControlLogix PLC racks, supplying stable multi-rail backplane power for CPU, communication and I/O modules. It achieves bumpless automatic failover; one unit fails while the other continues powering the chassis without interruption. The complete kit includes two 1756-PA75R power modules, two 1756-CPR2 redundant cables and one 1756-PSCA2 chassis adapter.

1756-PAR2
Key Features & Benefits
- Input: 85–265 VAC wide-range AC, 47–63 Hz, 75W per power unit
- Multi-rail output: 1.2 VDC / 3.3 VDC / 5.1 VDC / 24 VDC for ControlLogix backplane
- True hot redundancy, seamless switchover upon power module fault
- Each power module supports hot-swap for online maintenance
- LED status indication for power good, fault and redundancy health
- Built-in surge suppression, overvoltage, overcurrent and short-circuit protection
- Suitable for critical applications requiring uninterrupted control: power auxiliary, refining, chemical process
- UL, CE, cULus certified
Technical Specifications
| Item | Description |
|---|---|
| Manufacturer | Allen‑Bradley / Rockwell Automation |
| Model | 1756-PAR2 |
| Type | Redundant AC Power Supply Assembly |
| Input | 85–265 VAC, 47–63 Hz |
| Single Unit Power Rating | 75 W |
| Output Rails | 1.2VDC@1.5A; 3.3VDC@4A; 5.1VDC@13A; 24VDC@2.8A |
| Kit Contents | 2×1756-PA75R, 2×1756-CPR2, 1×1756-PSCA2 |
| Compatible Chassis | Standard 1756-A4 / A7 / A10 / A13 / A17 (NOT K-keyed AxxK chassis) |
| Operating Temperature | 0°C ~ +60°C |
| OEM Status | Active |
| Application | High-availability ControlLogix racks for process and power auxiliary control |
Typical Applications
1756-PAR2 is deployed on critical ControlLogix racks paired with CPU like 1756-L73 and 1756-L75K you listed before. It is widely used for boiler/turbine auxiliary control, motor sequence control and safety interlock racks in power plants and refineries. It eliminates single-point power failure risk and serves as a key outage spare.
Matching Companion Items
- Standard ControlLogix chassis 1756-A7 / A10
- 1756-L73 / 1756-L75 Logix CPU
- 1756 I/O modules and communication modules
- 1756-PAR2XT (extended temperature conformal coated variant)
- 1756-PDR2 (24VDC input redundant power kit)
Operation Notes
1756-PAR2 is for standard B-series chassis, it cannot be used on K-series AxxK chassis. Confirm adapter and cable version before replacement. After installation, test redundant failover function and alarm indication.
1756-PAR2K is the K-chassis redundant power counterpart, and 1756-PAR2XT is the wide-temperature coated version.
FAQ
Q: What is the difference between 1756-PAR2 and 1756-PAR2K? A: for standard chassis; PAR2K is for K-keyed chassis, not interchangeable. Q: Can I use only one power module from the kit? A: Yes, but redundancy function will be lost; full kit is required for redundant operation. Q: Can it supply power to Honeywell Experion or DeltaV racks? A: No, it is dedicated ControlLogix backplane power assembly.