106M1079-01 + 106M1081-01 (3500/15 Universal AC Power Supply Assembly)
Title
Bently Nevada 3500/15 Universal AC Power Supply Assembly, 106M1079-01 Power Converter Module + 106M1081-01 Universal AC Power Input Module, Hot‑Swappable Rack Power for 3500 Machinery Protection System
Technical Specifications
- Catalog Number: 106M1079-01 (Power Supply Module) + 106M1081-01 (AC PIM, Power Input Module)
- Assembly Part Code: 3500/15-05-05-00
- Brand: Bently Nevada (Baker Hughes)
- Product Type: Half‑height rack-mount universal AC power supply set for 3500 TSI rack
- AC Input Range: 85 ~ 264 VAC, 47–63 Hz, worldwide universal mains
- Output: Regulated low voltage DC to 3500 backplane, powers all monitor, relay and communication modules
- Max Power Capacity: Sufficient for full populated 3500 rack; supports single or redundant dual power arrangement
- Hot Swap: Yes, hot-swappable in redundant configuration without rack shutdown
- Mounting: Dedicated left half-height slots of standard 3500 chassis
- Status Indicator: Front panel “SUPPLY OK” LED
- Protection: Input surge, overvoltage, overcurrent, overtemperature, short-circuit protection
- Operating Temperature: -20 °C ~ +60 °C (-4 °F ~ +140 °F)
- Humidity: 5%–95% RH, non‑condensing
- Compliance: API 670, CE, EMC; suitable for turbine, compressor and pump protection cabinets
- Lifecycle Status: Active spare supported, mature legacy 3500 platform
- Country of Origin: USA
- Weight (Combined): ~1.8 kg
Key Features & Advantages
- Paired design: 106M1081-01 front-end AC input interface feeds 106M1079-01 DC conversion module; both must be matched as a complete AC power set.
- Wide universal AC input: Works on global plant mains 110 VAC / 220 VAC without jumper changes.
- Redundant power architecture support: Two complete 3500/15 assemblies can run in parallel for no-break power for critical machinery protection racks.
- Hot-swap capability: Redundant configuration allows replacement of one power assembly while the 3500 protection system remains online.
- Built-in fault diagnostics: Supply OK status available locally and via 3500 system software for remote alarm.
- API 670 compliant: Designed for safety-critical rotating machinery protection systems.
- Low noise regulated output: Clean backplane power minimises interference to proximity, velocity and acceleration monitor channels.
- Standard 3500 half-height form factor: Direct drop-in replacement for older 3500/15 AC supply variants.
Application Fields
- Steam / gas turbine and centrifugal compressor machinery protection cabinets
- Oil & gas refinery, pipeline and offshore rotating equipment monitoring
- Power plant boiler feed pump, generator and fan vibration protection
- Petrochemical process critical pump and expander TSI systems
- LNG compression and storage rotating machinery monitoring
- Pulp & paper, steel mill large rotating machine condition protection
- Retrofit and spare replacement for existing 3500 racks with universal AC supply requirement
- Safety instrumented machinery protection systems per API 670
Related Product Recommendations
- 133300-01: 3500/15 Low Voltage DC Power Input Module (DC version alternative)
- 133292-01: 3500/15 Low Voltage DC Power Supply Module
- 3500/22M: Transient Data Interface module
- 3500/42M: Vibration / Position Monitor module
- 3500/53: Relay Output module
- 3500/92: Communication Gateway module
- 3500 rack chassis and backplane
- 3500 System 1 monitoring software
- 3500/15 older legacy AC supply (127610-01, obsolete)
- 3500 surge protection terminal block for AC input
Installation & Maintenance
Installation
- The pair occupies two adjacent half-height dedicated power slots on the far left of the 3500 rack; 106M1081-01 (PIM) is the AC input front module, mated to 106M1079-01 converter behind it.
- Use shielded AC wiring; separate mains input cable from transducer coax, proximity probe and low-level signal cables.
- Torque AC input terminals correctly; verify input voltage is within 85–264 VAC before energising.
- For redundant setup, connect two independent AC source feeds to the two 3500/15 assemblies.
- Check the “SUPPLY OK” LED after power-up and confirm power health status in 3500 configuration software.
- Do not mix AC PIM (106M1081-01) with DC converter modules; AC and DC 3500/15 components are not interchangeable.
- Ensure rack cabinet ventilation is unobstructed to avoid thermal shutdown.
- Follow site electrical classification and hazardous area drawing requirements where applicable.
Maintenance
- During scheduled turnaround, inspect front LED status, AC terminal tightness and cabinet dust buildup.
- Monitor power fault alarms in System 1; intermittent supply OK alarms often indicate loose AC input, poor grounding or ageing supply.
- In redundant configuration, test single-supply failure by isolating one AC feed to verify seamless switchover.
- Keep spare complete matched sets (106M1079-01 + 106M1081-01); the two parts are sold and replaced as one AC power assembly.
- If replacement is required under redundancy, hot-swap procedure may be executed while the rack remains online; follow site lock-out / permit rules.
- After replacement, verify all monitor channels, relay outputs and communication remain healthy.
- Document power source arrangement, redundant test results and serial numbers in TSI system asset records.
- Do not disassemble modules internally; no field-serviceable parts inside.