Description
Product Title
Woodward EGCP-2, 8406-121 – Integrated Digital Genset Controller (50–150 VAC PT Input)
Core Product Introduction
The EGCP-2 (8406-121) is a microprocessor-based all-in-one engine-generator control package manufactured by Woodward, designed for diesel, gas and dual-fuel generator sets. It combines speed governing, voltage matching, synchronisation, real kW / reactive kVAR load sharing, automatic start-stop, sequence control and comprehensive engine & generator protection inside a single panel-mounted unit. This variant features 50–150 Vac PT sensing input, 9–32 Vdc control power supply, supporting standalone operation, utility paralleling and multi-unit genset networks up to 8 controllers for base load, peak shaving or standby power. Equipped with dual backlit LCD screens and membrane keypad for local monitoring, alarm check and parameter tuning. It supports Modbus RTU and RS422 ServLink communication for remote SCADA and configuration. This legacy controller is widely used as spare part replacement for marine, oil & gas, industrial power plants and critical backup power systems.

EGCP-2PN8406-121
Main Technical Specifications
| Item | Parameter |
|---|---|
| Model | EGCP-2 |
| Part Number | 8406-121 |
| PT Voltage Sensing | 50–150 VAC (differentiate from 8406-120:150–300Vac) |
| CT Current Input | 0–5 A RMS |
| Control Power | 9–32 VDC, nominal 24 VDC SELV |
| Display | Dual backlit LCD, membrane keypad |
| Max Networked Gensets | Up to 8 units for paralleling & sequencing |
| Communication | RS422 (ServLink), Modbus RTU |
| Operating Temperature | -20 °C ~ +70 °C |
| Storage Temperature | -40 °C ~ +105 °C |
| Humidity | 5%–95% RH, non-condensing |
| Enclosure | Front panel sealed aluminium housing |
| Dimension | 282 × 358 × 69 mm |
| Net Weight | ~2.9 kg |
| Mounting | Panel cutout mounting |
| Core Functions | Auto start/stop, synchronising, kW / kVAR load control, engine protection, genset electrical protection, alarm & shutdown |
| Certification | CE, marine approvals (DNV / ABS applicable for matched build) |
| Status | Discontinued OEM production, available for spare replacement |
Quality Control Procedure
- Visual & Label Inspection: Verify Woodward original marking, part number 8406-121, serial number, panel seal, no crack, burn trace, corrosion or terminal damage.
- Power Supply Burn-in Test: Apply adjustable 24 VDC power, confirm power boot sequence, LCD backlight, keypad response, no overheating or abnormal current draw.
- Analogue & I/O Terminal Check: Test discrete input / relay output channels, verify sensor loop response for oil pressure, coolant temp and speed pick-up signal.
- Voltage & Current Sensing Test: Inject simulated PT / CT signal to validate voltage, frequency and power metering accuracy.
- Communication Interface Test: Validate RS422 ServLink and Modbus RTU communication handshake with ServLink configuration software.
- Synchronisation & Load Control Simulation: Run bench simulation for sync window, governor bias and reactive power regulation logic.
- Alarm & Shutdown Logic Test: Trigger over-speed, low oil pressure, high coolant temperature, under/over voltage, over-frequency fault conditions to confirm alarm and shutdown action.
- Parameter Backup & Reset Check: Verify setpoint save / restore function.
- Static Packaging & QC Record: Anti-static bag + foam shock protection, serial-number traceable inspection report before shipment.
Frequently Asked Questions (FAQ)
Q1: What is the difference between 8406-121 and 8406-120?A1: 8406-121 = 50–150 Vac PT input (low voltage sensing); 8406-120 = 150–300 Vac PT input (high voltage sensing). They are not interchangeable without PT transformer modification and configuration adjustment.
Q2: Is EGCP-2 still in production?A2: The EGCP-2 series is discontinued by Woodward. Direct replacement is easYgen-3200XT with dedicated conversion kit for retrofit projects. Stock units are for legacy spare support.
Q3: What software do I use to program EGCP-2 8406-121?A3: Woodward ServLink software via RS422 cable (5417-551). Modbus RTU is available for SCADA monitoring only.
Q4: How many generators can parallel together?A4: Maximum 8 controllers can be networked for automatic sequencing and load sharing.
Q5: Can this unit work with both diesel and gas engines?A5: Yes, it supports diesel, natural gas and dual-fuel engines when matched with compatible speed actuator and AVR.
Q6: Does it support hot swap during running?A6: No. This is a panel-mounted integrated controller. Power must be isolated before removal.
Installation & Configuration Guide
- Pre-install Preparation: Confirm panel cutout dimension, 24 VDC clean power supply, shielded wiring for PT/CT/speed pick-up signal, ESD protection. Prepare ServLink software and 5417-551 RS422 communication cable.
- Panel Mounting: Secure the into control cabinet cutout, fasten locking clips, maintain ventilation clearance around rear terminals.
- Wiring Routing: Separate high-power actuator wiring from PT, CT and communication shielded cables. Follow manual polarity for PT voltage transformers and CT current transformers.
- Sensor & Actuator Termination: Connect magnetic speed pickup, oil pressure, coolant temperature discrete inputs, fuel actuator drive output and AVR raise/lower control signals.
- Power Up Initialisation: Apply 24 VDC control power. Confirm LCD lights up, self-test passes, no active fault alarms.
- Basic Setpoint Configuration: Access local keypad menu or ServLink software: engine rated speed, genset rated voltage, CT/PT ratio, alarm thresholds, shutdown delays.
- Governor & Voltage Tuning: Adjust speed gain, droop setting, voltage bias and VAR control parameters for stable frequency and voltage during load change.
- Synchronisation Setup (Paralleling Application): Enable sync function, configure voltage window, frequency window, phase angle window and closing time for breaker closure.
- Multi-unit Network Setup: Assign unique Modbus / network address for each , connect network communication bus, enable load sharing logic.
- Commissioning & Backup: Complete dry contact test, no-load test, load step test and fault trip test. Save the full configuration file via ServLink for site backup.
Warning: CT secondary circuit must never be opened while energised. PT wiring must be fused.
Related Woodward Models & Order Number Recommendation (15 pcs)
| Model | Order Number | Description |
|---|---|---|
| EGCP-2 | 8406-120 | EGCP-2 Controller, 150–300 VAC PT Input |
| EGCP-2 | 8406-123 | EGCP-2 variant, 50–150 VAC PT Input |
| EGCP-2 Connector Kit | 8928-301 | Terminal & connector accessory kit for EGCP-2 |
| RS422 Cable | 5417-551 | ServLink communication cable for EGCP-2 |
| easYgen-3200XT | 8440-1900 | Drop-in retrofit replacement for EGCP-2 |
| easYgen-3400XT | 8440-1902 | Advanced genset parallel controller |
| 2301A | 9905-003 | Digital speed governor |
| 2301D | 9907-018 | Load sharing & speed controller |
| 505 | 9907-162 | Steam turbine controller |
| 723PLUS | 9907-838 | Engine speed governor |
| ProAct-GP | 1762-802 | Electric actuator for gas engine |
| Actuator 8270 | 8270-101 | Fuel actuator for diesel engine |
| SPM-D11 | 8440-1631 | Synchroniser & load share module |
| DSS-2 | 8440-1552 | Digital synchronising unit |
| MPU Sensor | 1701-005 | Magnetic speed pickup for EGCP-2 |