Description
UES815S-24AR, Emerson EPRO UES815S Series Plug-in Regulated Power Supply, dedicated for EPRO TSI machinery monitoring rack
Core Product Introduction
The UES815S-24AR is a rack-mounted plug-in power supply developed by EPRO (Emerson), specially designed for EPRO MMS / AMS TSI vibration monitoring rack, supplying stable 24VDC power for TSI measurement cards, speed channels, proximity probe circuits and backplane bus. It adopts wide-range AC input, high isolation and multi-level protection design. This AR variant is the revised version of UES815S-24A, optimized for long-term continuous operation in turbine, compressor and other rotating machinery protection systems. Widely used in power plant, oil & gas, petrochemical rotating equipment condition monitoring & protection cabinets, matched with EPRO MMS6000 series TSI rack.

UES815S-24AR
Main Technical Specifications
| Item | Parameter |
|---|---|
| Part Number | UES815S-24AR |
| Manufacturer | Emerson (EPRO, Germany) |
| Type | Rack plug-in regulated power supply |
| Input | 85–264 VAC, 47–63Hz |
| Output | 24 VDC |
| Rated Output Current | 15 A |
| Isolation | Input-output reinforced isolation |
| Protection | Overload, short-circuit, overvoltage, over-temperature auto-shutdown |
| Cooling | Natural convection cooling |
| Mounting | Plug into EPRO TSI rack backplane |
| Hot Swap | Supported |
| Operating Temperature | -20 °C ~ +60 °C |
| Storage Temperature | -40 °C ~ +85 °C |
| Humidity | 5%–95% RH, non-condensing |
| Certifications | CE, cULus |
| Lifecycle Status | Obsolete / EOL, only spare stock available |
| Weight | ~1.4 kg |
Quality Control Procedure
- Visual & Label Inspection: Verify original EPRO/Emerson marking, UES815S-24AR part number, serial sticker, front panel LED window, edge connector without pin bending or corrosion.
- AC Power Boot Test: Apply wide-range AC input, confirm power LED steady on, 24V output stable, no abnormal noise or overheating.
- Load Regulation Test: Test output voltage under light load, 50% load and full 15A rated load, check voltage stability.
- Ripple & Noise Test: Measure output ripple, ensure it meets TSI low-noise requirement for proximity probe circuits.
- Protection Function Test: Trigger short-circuit / overload, verify power supply latch-off or auto-recovery protection.
- Over-temperature Simulation Test: Check thermal shutdown protection when temperature rises.
- Backplane compatibility test: Insert into MMS6000 rack, confirm normal power distribution to all TSI cards.
- Isolation withstand voltage test: Verify input-output isolation strength.
- Revision difference check: Confirm hardware revision AR, distinguish from older UES815S-24A.
- Packaging & Traceability: Anti-static packaging, foam protection, serial-number QC report before shipment.
Frequently Asked Questions (FAQ)
Q1: What is the difference between UES815S-24A and UES815S-24AR?A1: UES815S-24AR is the revised upgraded version of UES815S-24A, optimized for component reliability and thermal design; pin definition, rack compatibility and 24V/15A output parameters are fully consistent, can be used as direct replacement.
Q2: Which TSI rack is it used for?A2: It is designed for EPRO MMS6000 rack system, powering MMS6220, MMS6312, MMS6120 and other TSI monitoring modules. Not compatible with AMS6500 ATG rack power A6500-PS.
Q3: Can it be hot swapped when the TSI rack is running?A3: Hardware supports hot swap. But during replacement, all TSI cards in the rack lose power, which will trigger machine protection trip. MOC, trip bypass and alarm suppression must be completed before replacement.
Q4: Can it be used as an ordinary DIN-rail 24V power supply?A4: No, it is a special rack plug-in module with dedicated backplane connector, cannot install on standard DIN rail directly.
Q5: Is it interchangeable with Bently Nevada 3500 rack power?A5: Not interchangeable, different rack backplane, connector and internal power architecture.
Q6: What is the replacement plan when stock runs out?A6: Usually the whole MMS6000 rack is migrated to AMS 6500 ATG system with A6500-PS power module, or adopt external 24V industrial power supply with wiring modification.
Installation & Configuration Guide
- Pre-install Preparation: EPRO MMS6000 TSI rack, AC input source, screwdriver, MOC & turbine trip bypass procedure.
- Module Insertion: Align the edge connector and plug into the dedicated PSU slot of rack, lock front fixing screw.
- AC Input Wiring: Connect AC power to rack rear terminal, use shielded power cable and good protective earthing.
- Power Up: Switch on AC input, check front PWR LED is on, measure 24VDC output at backplane.
- Load Check: Check each TSI card powers up normally, no power-fault alarm on TSI modules.
- Full-load observation: Run under normal machine load for 30 mins, monitor temperature and output voltage.
- Fault simulation (commissioning only): Test short-circuit protection and auto recovery.
- Earthing confirmation: Ensure single-point earth for TSI rack to avoid ground loop interference to proximity probes.
- Online monitoring: Check TSI vibration, gap and speed signals are stable without noise jump.
- Backup: Record serial number, mark spare module, keep spare on site for emergency swap.
Warning: This power supply feeds safety-critical TSI protection cards. Unexpected power loss will cause loss of vibration, thrust and overspeed protection, which may lead to turbine/compressor trip. Always bypass protection before maintenance.
Related EPRO MMS6000 Series Models & Accessories (15 pcs)
| Model | Order Number | Description |
|---|---|---|
| Older power supply | UES815S-24A | Previous revision, compatible with AR |
| Vibration monitor card | MMS6220 | Shaft vibration TSI card |
| Shaft position / thrust card | MMS6312 | Axial displacement monitor |
| Speed & keyphasor card | MMS6120 | Speed and phase module |
| rack chassis | MMS-RACK-12 | 12-slot TSI rack |
| Proximity probe | CON021 + PR6423 | EPRO eddy current probe set |
| Probe extension cable | PR6424 | Probe extension cable |
| MMS communication card | MMS6823 | RS485 / Modbus comm interface |
| Rack backplane | MMS-BP | backplane |
| AC input terminal block | MMS-TERM-AC | AC input terminal accessory |
| MMS configuration software | -CFG | TSI parameter setup tool |
| 24V external backup PSU | SDN20-24-100 | Standalone 24V backup power |
| Signal isolation barrier | MMS-ISO | Probe signal isolator |
| Rack fan unit | MMS-FAN | Rack cooling fan |
| AMS6500 replacement power | A6500-PS | Power supply for AMS6500 ATG |