Description
TSXCUSBMBP Product Introduction
Overview
The TSXCUSBMBP is a Schneider Electric Modicon USB-to-Modbus Plus communication adapter. It acts as a network bridge that connects a PC/laptop USB port to legacy Modbus Plus industrial bus, enabling programming, firmware download, online monitoring and data exchange with Modicon Quantum PLCs and other Modbus Plus nodes. This adapter is OEM discontinued and widely supplied as surplus or refurbished spare for maintenance and commissioning of legacy Modicon control systems.

TSXCUSBMBP
Key Features & Benefits
- Transparent gateway between USB and Modbus Plus industrial network
- USB bus-powered design; no separate external DC power supply required
- Equipped with front-panel status LEDs for power and Modbus Plus bus activity diagnosis
- Functions as an independent Modbus Plus network node with configurable unique node address
- Compatible with Schneider Unity Pro / EcoStruxure Control Expert for PLC programming, upload/download and online debugging
- Supports firmware OS loading for Modicon Quantum CPU
- Robust industrial-grade enclosure for field commissioning in plant control rooms
- Simple point-to-point or multi-drop connection into existing Modbus Plus trunk networks
Technical Specifications
| Item | Description |
|---|---|
| Manufacturer | Schneider Electric (Modicon) |
| Model | TSXCUSBMBP |
| Type | USB to Modbus Plus Adapter / Gateway |
| Host Interface | USB 1.1 / 2.0 |
| Field Bus | Modbus Plus |
| Connector | USB Type A, DB9 Modbus Plus port |
| Power Supply | USB bus powered |
| Status Indicator | Power LED, Modbus Plus activity LED |
| Supported PLC | Modicon Quantum, legacy Modbus Plus devices |
| Software | Unity Pro, EcoStruxure Control Expert, MBX driver suite |
| OEM Status | Discontinued, available as surplus / refurbished spare |
| Application | PLC commissioning, troubleshooting, firmware upgrade, data acquisition |
Typical Applications
TSXCUSBMBP is mainly used by service engineers for on-site maintenance of Modicon Quantum PLC systems in power plants, water treatment and manufacturing facilities. Common tasks include downloading control logic, uploading program backups, viewing real-time variables, fault diagnosis and updating CPU operating systems over Modbus Plus bus. It is an essential spare communication tool for legacy Schneider Modbus Plus installations.
Matching Companion Items
- Modicon Quantum CPU and I/O racks
- Modbus Plus trunk cable, terminating resistors
- Unity Pro / EcoStruxure Control Expert programming software
- MBX Modbus Plus driver package
Operation Notes
The dedicated MBX driver must be installed on the PC before hardware connection. Each adapter requires a unique node address on the Modbus Plus network; duplicate addresses will cause bus conflict and communication failure. It is designed for engineering commissioning use, not permanent fixed-bus deployment.
FAQ
Q: Can TSXCUSBMBP work for standard Modbus RTU? A: No. It is exclusively for Modbus Plus, which is a proprietary token-passing bus different from Modbus RTU. It cannot connect directly to ordinary Modbus RTU instruments.
Q: Is it compatible with new M580 PLC? A: M580 does not natively support Modbus Plus; this adapter is primarily for legacy Quantum platforms.
Q: Can it communicate with DeltaV, Honeywell C300 or GE turbine boards? A: No native interoperability. It only serves Modbus Plus network devices.