Description
HONEYWELL SPS5710 (51198685-100) Power Supply Module | Experion PKS Series C Automation Spare Part
Product Brief Introduction
The HONEYWELL SPS5710, part number 51198685-100, is a high-performance 24VDC power supply module designed exclusively for Honeywell Experion PKS Series C DCS platform. It delivers regulated, stable 24V DC power to universal I/O modules, termination assemblies and rack electronics inside Series C cabinets. Featuring wide-range AC input, high efficiency and comprehensive built-in protection circuits, this unit supports redundant parallel operation to enhance power availability for continuous process control. Widely deployed in oil & gas, refining, chemical, power and pulp & paper facilities, it serves as a critical rack power spare for distributed control systems requiring 7×24 uninterrupted operation.

SPS5710 51198685-100
Key Technical Specifications
- Brand: HONEYWELL
- Model: SPS5710-2-LF
- Part Number: 51198685-100
- Product Type: Rack Power Supply Module
- Input Voltage: 100–240 VAC, 47–63 Hz
- Output: 24 VDC regulated
- Rated Output Current: 20 A
- Efficiency: ≥85%
- Operating Temperature: 0 °C ~ +60 °C
- Storage Temperature: -40 °C ~ +85 °C
- Relative Humidity: 5% – 95%, non-condensing
- Protection Functions: Overvoltage, overcurrent, overload, short-circuit auto-protection
- Hot Swap Support: Yes, hot-swappable in compatible Series C rack
- Mounting: Slot mount inside Honeywell Series C control cabinet
- EMC Compliance: IEC 61000 series
- Diagnostic: Front panel status LED, fault reporting via Experion system
- Redundancy: Supports N+1 redundant parallel configuration
- Certification: UL, CE, industrial lead-free design
Quality Control Procedure
- Visual & Marking Inspection: Check enclosure, label, connector pins and internal PCB for scratches, corrosion or mechanical damage.
- Input & Output Electrical Test: Verify output voltage accuracy under light load, rated load and transient load conditions.
- Protection Function Test: Trigger over-current and short-circuit conditions to confirm shutdown and recovery performance.
- Redundancy Parallel Test: Validate seamless load sharing between two SPS5710 units.
- Burn-in Screening: Continuous powered aging under rated temperature to expose early latent failures.
- EMC Noise Immunity Test: Simulate industrial electromagnetic interference environment.
- Firmware / Hardware Revision Confirmation: Confirm correct revision matching Series C cabinet firmware.
- Serial Number & Test Log Archiving: Record SN, test data and revision information for full traceability.
- ESD & Shock Protected Packing: Anti-static bag + foam cushion before shipment.
Frequently Asked Questions (FAQ)
Q1: What system is 51198685-100 SPS5710 used for?A1: It is dedicated power supply for Honeywell Experion PKS Series C DCS, powering universal I/O and IOTA assemblies.
Q2: Can this power supply be hot swapped online?A2: Yes, it supports hot swap within Series C rack when redundant power configuration is implemented, follow site LOTO and maintenance permit procedure.
Q3: Can multiple SPS5710 run in parallel?A3: Yes, it supports redundant parallel operation for N+1 power backup, avoiding total rack power loss upon single PSU failure.
Q4: What will happen if the fails?A4: Non-redundant rack will lose 24V I/O power and trigger DCS I/O offline alarms. Redundant configuration will automatically switch load to the standby unit without process interruption.
Q5: Is it compatible with older Honeywell DCS series such as TDC3000?A5: No. It is built for Series C Experion PKS only; it cannot be used for TDC3000 or Triconex SIS racks.
Q6: What is the standard warranty?A6: 12 months warranty after delivery. Extended warranty can be quoted separately.
Q7: Is the module sensitive to electrostatic discharge?A7: Yes. ESD wrist strap and anti-static workstation are mandatory during handling and replacement.
Installation & Configuration Guide
- Pre-Install Preparation
- Confirm rack is running under redundant power scheme (if hot swap is planned).
- Prepare ESD wrist strap, insulated screwdriver, maintenance work permit and cabinet wiring drawing.
- Inspect new (51198685-100) for physical damage and confirm part & revision.
- Remove the Faulty Power Module
- Locate the PSU slot inside Series C cabinet.
- Release front latch, slide the module out steadily along guide rails.
- Immediately place the defective PSU into an ESD shielding bag.
- Insert the New
- Keep ESD protection during the whole operation.
- Align the edge connector with backplane slot, push fully seated and lock front latch.
- Power & Status Verification
- The module will energize automatically in hot-swap scenario.
- Check front LED indicator: Green = normal output; Red/Amber = fault, over-load or input loss.
- Log into Experion PKS station, check cabinet health display, confirm power supply status is healthy.
- Verify load sharing balance if running in redundant parallel mode.
- Load & Loop Test
- Check all I/O modules in the rack power up normally.
- Monitor 24VDC bus voltage for stability under full load.
- Simulate input power loss of one PSU to confirm seamless redundant switchover.
- Post-Install Handover
- Clear fault alarms, record serial number, revision and replacement time in maintenance log.
- Confirm no I/O point abnormal status, hand cabinet back to operation team.
Important Reminder: If the rack is configured with single power supply, cut off cabinet main AC power before replacement, perform strict LOTO lockout-tagout.
Related Honeywell Models & Part Number Recommendations (15 pcs)
- 51198685-100 Power Supply
- 51199929-100 SPS5711 Power Supply
- 51199946-100 24V Battery Backup Kit
- CC-PUIO01 Universal I/O Module
- CC-TDIL01 Digital Input IOTA
- CC-TDOL01 Digital Output IOTA
- CC-TAIX01 Analog Input IOTA
- CC-TAOX01 Analog Output IOTA
- CC-PAOH01 HART Analog Output Module
- CC-PDIL01 Digital Input Module
- CC-PDOL01 Digital Output Module
- CN100 Control Network Module
- CC-PCNT02 C300 Controller
- 51199472-100 Backplane Assembly
- 51204166-100 Series C Fan Module