Description
HIMA F3236 (984323602) 16‑Channel SIL3 Safety Digital Input Module
Product Introduction
The HIMA F3236 is a 16-channel safety digital input module for HIMA Planar / HIMatrix safety systems, certified SIL3 per IEC 61508. It acquires 24 VDC discrete safety signals in two modes: dry contact switch input or 6 mA current-loop sensor input. Adopting 1oo2D safety architecture, it provides per-channel diagnostics including wire-break detection and short-circuit monitoring. Galvanic isolation between field wiring and backplane bus improves noise immunity. It supports hot swap and is widely used in ESD, F&G and BMS safety loops in process plants. It is a critical spare for maintenance and retrofit of legacy HIMA safety instrumented systems.

F3236 (984323602)
Specification Parameters
| Item | Specification |
|---|---|
| Brand | HIMA (Germany) |
| Model | F3236, Order No: 984323602 |
| Type | Safety Digital Input Module |
| Channels | 16 independent DI channels |
| Input modes | Dry contact / 6 mA current loop (24 VDC nominal) |
| Safety Level | SIL3 (IEC 61508), Cat.4 (EN 954-1) |
| Typical response time | 8 ms |
| Isolation | 1500 VAC field to backplane |
| Max line resistance | 11 Ω per channel |
| Power supply | 5 VDC / 24 VDC from rack backplane |
| Mounting | Planar rack, 4TE form factor |
| Hot Swap | Supported |
| Operating temperature | -20 °C ~ +60 °C |
| Certifications | TÜV, ATEX II 3G Ex nA, CE |
| Weight | Approx. 0.28 kg |
Application Scenarios
- Emergency Shutdown System (ESD) signal collection
- Fire and Gas (F&G) detection and alarm loops
- Burner Management System (BMS) safety interlocks
- Petrochemical and refinery safety instrumented systems
- Onshore & offshore oil & gas platform SIS cabinets
- Power plant turbine protection and safety interlock
- Chemical continuous process safety monitoring
- Spare replacement for existing HIMA Planar racks
Recommended 10 Related Models
- F3240 – 16-channel DI module for 110VDC / 127VAC contacts
- F3330 – 16-channel safety digital output module
- F6217 – Analog input safety module
- F6705 – Analog output safety module
- F7126 – Communication interface module
- F7133 – Power supply module for Planar rack
- F8627X – HIMatrix CPU controller
- F8650X – High-end HIMatrix safety CPU
- F8652X – Redundant HIMatrix controller
- Z7116 – Termination adapter cable
FAQ
Q1: What are the two input types of F3236? A1: Dry contact (mechanical switch) and 6 mA current-loop 1-signal sensors, both 24 VDC field side.
Q2: Can F3236 be hot swapped? A2: Yes, it supports hot-swap replacement on the Planar rack, following HIMA SIS maintenance procedure. Safety bypass must be applied for related safety loop.
Q3: What system platform does F3236 belong to? A3: It belongs to HIMA Planar legacy rack system, compatible with H41q / H51q safety controllers.
Q4: Is it SIL3 certified? A4: Yes, the module itself is SIL3 certified. The full safety loop must be verified in accordance with the safety manual.
Q5: Is discontinued? A5: Yes, Planar series is legacy and out of active production. Available stock is new surplus or fully tested refurbished spares.
Q6: Does it have channel diagnostics? A6: Yes, each channel supports wire break and circuit fault diagnosis for safety integrity monitoring.