Description
Fireye 85UVF1A-1QD, Phoenix II Ultraviolet Flame Scanner, 8-Pin Quick Disconnect Version
Core Product Introduction
The 85UVF1A-1QD is a microprocessor-based solid-state ultraviolet flame scanner from Fireye Phoenix Series 2, widely used in burner management systems (BMS) for gas, light oil and hydrocarbon combustion flames. It integrates flame sensing, signal processing, flame relay and diagnostics into one compact unit; no separate remote flame amplifier is required. The unit detects flame flicker modulation within the UV spectral band (295–340 nm), automatically calibrates on-target flame and sets on/off thresholds during commissioning. It provides relay status outputs plus a 4–20 mA analog signal proportional to flame strength. The QD variant uses an 8-pin quick-disconnect connector for fast field replacement and wiring, suitable for Class I Div 2 hazardous locations in refineries, power boilers, furnaces, heaters and process combustion packages.

85UVF1A-1QD
Main Technical Specifications
| Item | Parameter |
|---|---|
| Part Number | 85UVF1A-1QD |
| Manufacturer | Fireye (Honeywell) |
| Series | Phoenix Series 2 |
| Detection Principle | Ultraviolet (UV) solid-state sensor |
| Spectral Response | 295 ~ 340 nm |
| Supply Voltage | 24 VDC nominal (20.4 ~ 28.8 VDC) |
| Supply Current | Max 200 mA |
| Outputs | SPST NO Flame Relay; SPST NC Fault Relay; Isolated 4–20 mA flame strength |
| 4–20mA Max Load | 750 Ω |
| FFRT | Selectable flame failure response time |
| Electrical Interface | 8-pin QD quick-disconnect connector |
| Enclosure | Cast aluminum, grey polyester powder coating |
| Ingress Rating | IP66 / NEMA 4X |
| Operating Temperature | -40 °C ~ +65 °C |
| Relative Humidity | 5%–95% RH, non-condensing |
| Hazardous Approval | Class I Div 2 Gr A,B,C,D; Class II Div 2 Gr F,G |
| Certifications | UL, FM, CE, ATEX / IECEx |
| Mounting | 1” NPT threaded mount (flange/nipple ordered separately) |
| Weight | 2.69 kg |
| Lifecycle Status | Active spare & new build |
Quality Control Procedure
- Visual & Label Inspection: Verify original Fireye marking, part number 85UVF1A-1QD, serial number, housing integrity, lens surface, QD connector pins, no scratches, dents or corrosion.
- Power Boot Test: Apply regulated 24 VDC supply, confirm power LED, startup self-test sequence, no overheating or abnormal current draw.
- Internal Self-Check Function Test: Verify built-in electronic self-test cycle triggers fault relay and fault LED correctly.
- UV Response Bench Test: Use calibrated UV flame simulator to test flame detection; confirm flame relay pulls in and 4–20mA output rises proportionally.
- Flame Loss / FFRT Test: Remove UV source, validate flame dropout within configured response time, relay de-energizes correctly.
- Relay Contact Test: Check continuity of flame NO relay and fault NC relay contacts under rated resistive load.
- 4–20mA Analog Calibration: Confirm 4 mA = no flame, 20 mA = maximum flame strength, linearity within tolerance.
- LED Diagnostic Check: Validate power, flame present, fault status indicators.
- Housing & Seal Inspection: Verify gasket integrity for IP66 sealing.
- Packaging & Traceability: Anti-static packing, protective foam, serial-number linked QC report before shipment.
Frequently Asked Questions (FAQ)
Q1: What flame types is 85UVF1A-1QD suitable for?A1: Optimized for gas and light oil hydrocarbon flames. Not suitable for clean hydrogen flames with minimal UV emission; select IR scanner models for hydrogen applications.
Q2: What is the difference between 85UVF1A-1QD and 85IRF1A-1QD?A2: 85UVF = ultraviolet sensor; 85IRF = infrared sensor. UV is better for gas/oil; IR works for smoky, low-UV or hydrogen flames, they are not interchangeable.
Q3: What cable do I use for the QD connection?A3: Requires Fireye 59-546 series 8-pin quick-disconnect cable. Do not hardwire directly to terminals.
Q4: Is this an Ex d flame detector?A4: 85UVF1A-1QD is Class I Div 2 / Ex nA for non-incendive hazardous area. For Zone 1 / Ex d applications, select the CEX explosion-proof variant.
Q5: Does it need an external flame amplifier?A5: No, this is an integrated scanner with internal flame relay and onboard processing. It can wire directly to BMS logic or PLC DI inputs.
Q6: Can I clean the viewing lens on site?A6: Yes, use a soft lint-free cloth. Contamination of the UV lens causes loss of flame signal and false flame failure trips. Keep cooling purge air supply if installed.
Installation & Configuration Guide
- Pre-install Preparation: 24 VDC power supply, matching 59-546 QD cable, 1” NPT mounting flange/nipple, purge air fitting (if required), BMS wiring diagram.
- Mechanical Mounting: Thread scanner into burner sight port, align optical line of sight directly to the flame root; avoid viewing refractory reflection.
- Purge Air Setup (Recommended): Connect instrument air purge to prevent soot, dust and heat damage to the UV lens; maintain specified flow rate.
- QD Cable Connection: Mate the 8-pin quick disconnect firmly, ensure locking collar is tightened.
- Wiring to BMS: Wire 24VDC power, flame relay, fault relay and 4–20mA analog loop to burner management system or PLC analog input card.
- Power Up: Energize 24 VDC supply; scanner runs automatic power-up self-test. Confirm no fault alarm.
- Auto Learn / Teach Sequence: Light the target flame, initiate the scanner learn cycle. The unit automatically stores flame signature, gain and trip thresholds.
- FFRT Configuration: Set flame failure response time according to burner safety requirements per local code.
- Commissioning Test: Perform flame present test and flame loss trip test; verify relay status, 4–20mA value and BMS trip sequence.
- Site Documentation: Record learned flame signature, FFRT setting, purge air pressure and scanner serial number in burner package file.
Warning: UV scanners can be blinded by direct sunlight or arc welding UV radiation. Ensure sighting geometry avoids external UV sources. Follow local boiler and burner safety codes for BMS commissioning.
Related Fireye Phoenix Series Models & Order Number Recommendation (15 pcs)
| Model | Order Number | Description |
|---|---|---|
| IR Flame Scanner QD | 85IRF1A-1QD | Phoenix II infrared flame scanner, 8pin QD |
| UV Explosion Proof Scanner | 85UVF1A-1CEX | Ex d UV flame scanner for Zone 1 |
| IR Explosion Proof Scanner | 85IRF1A-1CEX | Ex d infrared flame scanner |
| UV K3 Coated Version | 85UVF1A-1QDK3 | Conformal coated UV scanner for corrosive atmosphere |
| IR K3 Coated Version | 85IRF1A-1QDK3 | Conformal coated IR scanner |
| QD Connection Cable | 59-546-1 | 8-pin QD scanner cable, standard length |
| 1” NPT Mount Flange | 60-2919-1 | Mount nipple/flange with purge air port |
| Cooling Purge Nipple | 60-2920-1 | Extended sight tube assembly |
| Phoenix Programming Tool | ED510 | Fireye handheld configurator for Phoenix scanners |
| UV Scanner Window Kit | 60-2925 | Replacement UV lens and gasket kit |
| Stainless Housing UV Scanner | 85UVF4A-1QDWR | Stainless steel body UV flame scanner |
| Stainless IR Scanner | 85IRF4A-1QDWR | Stainless infrared flame scanner |
| BMS Amplifier Module | EP260 | Fireye burner control amplifier |
| Flame Signal Display Unit | ED600 | Remote flame strength indicator |
| Purge Air Regulator | 60-2930 | Air regulator for scanner lens purge |