Description
Allen‑Bradley 2711P‑K10C6D1 PanelView Plus 6 1000 Keypad Color HMI Terminal, 10.4‑inch, DC Powered, Expandable Communication Module Slot

2711P-K10C6D1
Technical Specifications
- Display: 10.4” Color TFT LCD, 640 × 480 VGA
- Input: Industrial membrane keypad (no touch overlay), numeric + function keys
- Power Supply: 18–32 VDC
- Memory: 64 MB RAM, onboard Flash + CompactFlash slot for application / firmware storage
- Operating System: Windows CE, configured for FactoryTalk View Machine Edition (ME) runtime
- Communication: Integrated Ethernet, RS‑232 serial; expansion slot for optional communication daughtercards (DH+, RIO, ControlNet)
- USB: 1 × USB host port for storage, keyboard, printer
- Front Panel Rating: NEMA 4X, 12, 13; IP65 (front only)
- Ambient Operating Temp: 0 °C to +50 °C
- Storage Temperature: −20 °C to +70 °C
- Humidity: 10–90 %, non‑condensing
- Mounting: Panel cutout mounting
- Backlight: Field‑replaceable CCFL backlight
- Software: Programmed by FactoryTalk View ME
- Weight: Approx. 2.6 kg
- Note: Discontinued original unit; widely supplied as surplus / refurbished / tested spare
Application Scenarios
- Legacy Rockwell automation systems with ControlLogix, PLC‑5, SLC‑500
- Oil & gas, refinery and petrochemical process control
- Power plant auxiliary control and boiler monitoring
- Pulp & paper continuous process lines
- Food & beverage batch production
- Mining and bulk material handling
- Water / wastewater treatment plants
- Automotive assembly and heavy machinery requiring keypad operation (gloved hand use)
Installation and Maintenance
- Installation: Panel cutout mounting in a control cabinet; maintain side/top/bottom clearance for convection cooling; seal front gasket properly to preserve NEMA 4X / IP65 rating; isolate power and signal wiring; shielded cable recommended for serial and Ethernet; compatible with standard PanelView Plus 1000 cutout footprint
- Maintenance: Periodically inspect gasket integrity, keypad wear, backlight brightness and cable tightness; clean front panel only with approved mild cleaners; backup HMI application to CompactFlash or USB before firmware upgrade; replace failed backlight or display module with certified spare parts; no field repair of logic board; faulty units should be returned for authorized refurbishment; avoid condensation and corrosive gas environments; power down before swapping communication modules
Related Models
- 2711P‑T10C6D1 / 2711P‑T10C6D2: Touch version of the same expandable 10.4” PV+6
- 2711P‑B10C6D1: Combined keypad + touch 10.4” PV+6
- 2711P‑K10C4D1: Standard Ethernet/RS232 keypad model (no expansion comm slot)
- 2711P‑RDK10C: 1000 keypad color display replacement module
- 2711P‑RP8D: Matching DC logic module
- Migration alternatives: 2711P‑T10C21D8S (PanelView Plus 7 Standard), 2715P‑B10CD (PanelView 5510)
- Spare: 2711P‑RL10C, field‑replaceable backlight for 10.4” color display