Description
ABB TC560V2 3BSE022178R1 Optical Modem for Advant Fieldbus 100 (AF100) ModuleBus
Model & Part Number
- Type: TC560V2
- Order Code: 3BSE022178R1
- Manufacturer: ABB
- Product Category: Optical Modem / Bus Repeater
- Compatible System: ABB Advant Master DCS, AC160, AC450, S800 I/O, Advant Fieldbus 100 (AF100)
- Replacement for: TC560 3BSE004730R1

TC560V2 3BSE022178R1
Product Description
The TC560V2 (3BSE022178R1) is an upgraded optical modem designed for ABB Advant Fieldbus 100 ModuleBus. It converts electrical AF100 bus signals to optical signals and vice versa, extending communication distance and isolating electrical noise, ground potential difference and surge interference between control nodes and remote S800 I/O racks. This unit is widely deployed to connect remote I/O clusters via fiber optics in Advant Master DCS architecture. It is an end-of-life legacy component, and most global demand comes from plant spare replacement, system overhaul and life extension of existing Advant Master installations.
Technical Specifications
| Item | Specification |
|---|---|
| Bus Protocol | Advant Fieldbus 100 (AF100) ModuleBus |
| Function | Electrical ↔ Optical media conversion |
| Fiber Interface | Single-mode optical port |
| Transmission Rate | AF100 native bus speed |
| Power Supply | 24 VDC, 19.2 ~ 30 VDC |
| Mounting | DIN rail / rack mounting inside control cabinet |
| Operating Temperature | 0°C ~ +55°C |
| Storage Temperature | -40°C ~ +70°C |
| Relative Humidity | 5% ~ 95%, non-condensing |
| Protection Class | IP20 |
| Net Weight | Approx. 0.75 kg |
| Compliance | CE certification |
| Diagnostic | Status LED indicators for power, bus link and fiber fault |
Application Fields
- Thermal power plants and combined cycle power units
- Oil & gas production, refining and petrochemical complexes
- Pulp and paper process plants
- Cement, mining and mineral processing
- Metallurgy and steelmaking
- Water and wastewater treatment
- Large-scale chemical process facilities
- Legacy Advant Master DCS remote I/O extension and retrofit
Brand Profile (ABB Advant Master)
ABB Advant Master DCS platform was one of the flagship process control systems launched in the 1990s, including AC110, AC160, AC450 controllers, AF100 fieldbus and S800 distributed I/O. is the core high-speed fieldbus for connecting controllers and remote I/O stations. TC560V2 optical modem is a key accessory to break the distance limit of twisted-pair bus. While ABB System 800xA is the modern successor, a huge installed base of Advant Master systems still relies on optical modems for stable operation.
Related News & Industry Events
TC560V2 3BSE022178R1 has been discontinued by ABB. Original new stock is scarce, and supply chain volatility pushes end-users to stock tested spare modems. Many power and refinery sites separate remote S800 I/O racks far from control rooms, so fiber media converters like TC560V2 are critical to avoid bus interruption. Plant owners normally evaluate migration to System 800xA during turnaround, while maintaining spare inventory of to mitigate outage risk during transition. Refurbished and fully tested units remain popular aftermarket spares for Advant Master operators.
Usage Scenarios
- ModuleBus media conversion between copper twisted pair and optical fiber
- Long-distance connection of remote S800 I/O racks away from main control room
- Electrical isolation between control cabinets with different ground potentials
- Noise suppression for bus in high EMI areas such as turbine halls and substations
- Direct replacement for failed TC560 / optical modem during maintenance outage
- Expansion of Advant Master DCS with additional remote I/O clusters
- Redundant fiber bus link construction for critical control loops
- On-site troubleshooting and bus signal regeneration
Functional Advantages
- Native protocol support, plug-and-play for Advant Master ModuleBus
- Optical isolation eliminates ground loop interference and common-mode noise
- Greatly extends communication range compared with copper cable
- Built-in LED diagnostics for quick fault identification of power, copper bus and fiber link
- Rugged industrial design for continuous 24/7 operation in process cabinets
- DIN rail compact mounting, easy integration with existing S800 rack layout
- Backward compatible with older TC560 (3BSE004730R1)
- Low power consumption, stable signal regeneration
- Reduces risk of bus failure caused by lightning surge and transient voltage
Recommended Related Products (16 pcs)
- ABB TC560 3BSE004730R1 Optical Modem
- ABB TC561V2 3BSE022179R1 Optical Modem
- ABB TC514V2 3BSE013281R1 Opto Repeater
- ABB TC512V1 3BSE018059R1 RS485 Modem
- ABB PM665 3BDS005799R1 AC160 Processor
- ABB PM664 Processor Module
- ABB CI854 3BSE040662R1 Profibus Interface
- ABB DI801 3BSE013230R1 Digital Input
- ABB DO801 3BSE013231R1 Digital Output
- ABB AI810 3BSE008516R1 Analog Input
- ABB AO810 3BSE008520R1 Analog Output
- ABB SD832 3BSE018103R1 Power Supply
- ABB SD833 3BSE018105R1 Power Supply
- ABB TK802 Bus Cable
- ABB TU810 3BSE020508R1 Terminal Unit
- ABB AC450 Controller Module
Installation Instruction
- Disconnect the 24 VDC power supply of the bus rack before installation.
- Mount firmly on standard DIN rail inside the control cabinet.
- Wire 24 VDC power terminals strictly following polarity requirements.
- Connect the twisted-pair bus cable to the electrical side terminal; use shielded twisted pair and proper bus termination resistor.
- Insert fiber connector into optical port, check fiber cleanliness and avoid bending fiber beyond minimum bend radius.
- Pair two modems at both ends of the fiber link for bidirectional conversion.
- Restore power and observe status LEDs: confirm power OK, copper bus active and fiber link established.
- Verify bus communication, check that all remote I/O modules are detected by controller.
- Monitor bus quality for a period; check no packet loss or intermittent dropout.
- Secure cable routing, separate fiber and power cables to reduce crosstalk.
- Label both ends of fiber and copper bus for future maintenance.
- Close cabinet door to maintain IP20 protection and EMI performance.
Maintenance Guide
- Daily Check: Inspect LED status, check for loose terminals, dust accumulation and fiber connector contamination.
- Periodic Maintenance: Clean module surface with dry anti-static brush; clean fiber end face with professional fiber cleaning tool. Do not use liquid cleaner on optical interface.
- Routine Test: Verify bus communication during planned shutdown; record link status of all fiber segments.
- Troubleshooting: If fiber fault LED is on, inspect fiber breakage, connector dirt or misalignment first. For copper bus fault, check bus termination, shielding, ground loop and other modems on the same bus.
- Spare Handling: Store standby in anti-static packaging, dry and cool environment, protect optical ports with dust caps.
- Repair Notice: Do not disassemble internal optical transceiver components on site. Return faulty unit to qualified automation vendor for testing and replacement.
- Lifecycle Note: is obsolete optical modem. Prepare DCS migration plan to System 800xA while maintaining spare stock for risk control.