ABB PM861AK01 (3BSE018157R1) AC 800M Processor Unit Kit

Model Order Number Description
PM861K01 3BSE018105R1 PM861 Processor Unit Kit (Non-A version)
PM864AK01 3BSE018161R1 High-performance AC800M Processor Kit
PM866K01 3BSE025349R1 Top-range AC800M Controller Kit
PM856K01 3BSE018104R1 Mid-range AC800M Processor Unit Kit
CI853 3BSE018103R1 PROFIBUS-DP Communication Interface
CI854A 3BSE030220R1 AF100 Communication Interface
CI854B 3BSE069449R1 Upgraded AF100 Interface Module
CI855 3BSE018106R1 Modbus Master Interface
CI857 3BSE018144R1 Interbus Communication Module
CI858 3BSE018135R1 DeviceNet Interface
TP830 3BSE018155R1 Baseplate for PM861A
SB821 3BSE008508R1 External Backup Battery Unit
TB850 3BSE018164R1 CEX Bus Terminator
TB807 3BSE018163R1 ModuleBus Terminator
TK851 3BSE020508R1 Redundant RCPU Link Cable
Category: SKU: ABB PM861AK01 (3BSE018157R1) Brand:

Description

ABB PM861AK01 (3BSE018157R1) AC 800M Processor Unit Kit

 

Core Product Introduction

The PM861AK01 (3BSE018157R1) is a complete processor kit for ABB AC 800M distributed control system, built around the PM861A CPU module. It is a 32-bit RISC controller designed for process automation, oil & gas, power, pulp & paper, and heavy industrial applications. This kit comes pre-packaged with CPU, TP830 baseplate, bus terminators, backup battery and power connector, ready for direct installation. It supports 1:1 hot redundancy with fast switchover, dual Ethernet control network, S800 I/O expansion, and CompactFlash program backup. Widely used for legacy system spare replacement, controller upgrade and new small-to-medium DCS control nodes. It complies with global industrial standards and hazardous location certifications for reliable continuous operation.

ABB PM861K01 3BSE018105R1

Main Technical Specifications

Item Parameter
Type PM861AK01 Processor Unit Kit
Order No. 3BSE018157R1
CPU Core MPC860, 32-bit RISC, 48 MHz
RAM 16 MB SDRAM
Flash Memory 8 MB for firmware & application
Application Available Memory ~7.15 MB
Storage Interface CompactFlash slot for backup & download
Ethernet Ports 2 × RJ45, 10 Mbps control network
Serial Ports COM3 (RS232 general), COM4 (isolated RS232 service port)
Power Supply 24 V DC, 19.2 ~ 30 V DC tolerance
Power Consumption Typ. 6 W, Max. 10.3 W
Redundancy 1:1 redundant support, <10ms switchover
Max S800 I/O Stations Up to 12 units via ModuleBus
Operating Temp 0 °C ~ +60 °C
Storage Temp -40 °C ~ +70 °C
Humidity 5% ~ 95% non-condensing
Protection Class IP20
Mounting DIN rail via TP830 baseplate
Kit Contents PM861A CPU, TP830 baseplate, TB850, TB807, TB852 terminators, backup battery, 4-pin power plug
Net Weight ~1.2 kg
Certifications CE, UL508, cULus Class I Div.2 / Zone 2, DNV, ABS, RoHS

 

Quality Control Procedure

  1. Visual & Document Inspection: Verify part number, label, serial number, packaging integrity, and original factory marking. Check no physical scratch, burn mark or corrosion on PCB and connector.
  2. Power Cycle Test: Apply regulated 24VDC power supply; confirm RUN / FAIL LED status, no overcurrent or abnormal heating.
  3. Communication Interface Test: Test dual Ethernet and isolated RS232 service port connectivity; verify bus terminator function.
  4. Redundancy Link Test: Pair with matched PM861 unit to validate RCPU link and redundant switchover performance.
  5. Memory & Backup Battery Check: Confirm RAM/Flash recognition, battery voltage and memory retention function.
  6. Firmware Compatibility Check: Load standard AC800M firmware to confirm normal initialization and CEX bus handshake.
  7. Environmental Screening (for critical stock): Short temperature cycling test, humidity soak test.
  8. Final Packaging & QC Report: Attach inspection record, anti-static sealing, shockproof packing before shipment. All units are traceable with serial number records.

 

Frequently Asked Questions (FAQ)

Q1: What is the difference between PM861AK01 (3BSE018157R1) and PM861K01 (3BSE018105R1)?A1: PM861AK01 is the upgraded A version with PM861A CPU; PM861K01 is the original PM861 version. They are not fully firmware cross-compatible.

Q2: Does this kit support hot swap?A2: The CPU module can be hot-swapped on the TP830 baseplate when the system is configured for redundancy. Single non-redundant node must be powered down before removal.

Q3: How long can the backup battery retain memory?A3: Standard internal battery supports minimum 118 hours data retention. External SB821 / SB822 battery can extend backup time for long power outage scenarios.

Q4: Can it work with S900 I/O?A4: PM861A is designed for S800 I/O via ModuleBus; S900 requires other AC800M controller models.

Q5: Is this unit suitable for Zone 2 hazardous area?A5: Yes, it carries cULus / AEx nA IIC T4 certification for Class I Zone 2, suitable for oil & gas and chemical hazardous locations.

Q6: What cable is needed for redundant CPU link?A6: TK851 or TK855 redundant link cable for RCPU connection between paired PM861A controllers.

 

Installation & Configuration Guide

  1. Pre-installation Preparation: Confirm ambient temperature, dust, vibration and ESD protection. Use anti-static wristband during handling. Prepare 24VDC regulated power supply, CCB (Compact Control Builder) programming software, Ethernet cable and TK851 redundancy cable if required.
  2. Mechanical Mounting: Clip TP830 baseplate onto standard DIN rail. Ensure sufficient clearance for ventilation (≥20mm top/bottom).
  3. Bus Terminator Installation: Install TB807 (ModuleBus), TB850 (CEX-bus), TB852 (RCPU-Link) terminators as per bus topology. Missing terminators cause unstable communication.
  4. Wiring: Connect 24VDC power plug; strictly separate control power and I/O power wiring. Ground the baseplate to protective earth.
  5. CPU Insertion: Slide PM861A CPU into TP830 baseplate and lock the latch. Do not force insertion.
  6. Power-up & Initialization: Apply 24VDC power. Observe LED sequence: INIT → RUN. If FAIL LED stays on, check power, terminator and bus short circuit.
  7. PC Connection & Configuration: Connect PC to COM4 isolated service port or Ethernet. Launch Compact Control Builder, assign controller IP, download hardware configuration and application program.
  8. Redundancy Setup (Optional): Mount second , connect TK851 cable, configure redundant pair in CCB, download redundancy settings and test failover.
  9. I/O Commissioning: Connect S800 I/O modules on ModuleBus, scan I/O nodes and verify channel status.
  10. Backup: Save project to CompactFlash card for on-site restore purpose.

Warning: Do not plug/unplug serial/Ethernet cables while high voltage is nearby. Remove power before replacing terminators or battery.

 

Related ABB AC800M Models & Order Number Recommendation (15 pcs)

Model Order Number Description
PM861K01 3BSE018105R1 PM861 Processor Unit Kit (Non-A version)
PM864AK01 3BSE018161R1 High-performance AC800M Processor Kit
PM866K01 3BSE025349R1 Top-range AC800M Controller Kit
PM856K01 3BSE018104R1 Mid-range AC800M Processor Unit Kit
CI853 3BSE018103R1 PROFIBUS-DP Communication Interface
CI854A 3BSE030220R1 AF100 Communication Interface
CI854B 3BSE069449R1 Upgraded AF100 Interface Module
CI855 3BSE018106R1 Modbus Master Interface
CI857 3BSE018144R1 Interbus Communication Module
CI858 3BSE018135R1 DeviceNet Interface
TP830 3BSE018155R1 Baseplate for PM861A
SB821 3BSE008508R1 External Backup Battery Unit
TB850 3BSE018164R1 CEX Bus Terminator
TB807 3BSE018163R1 ModuleBus Terminator
TK851 3BSE020508R1 Redundant RCPU Link Cable