Description
ABB PM851K01 — 3BSE018168R1
Brand / Model: ABB PM851K01
Order Code: 3BSE018168R1
Product Family: AC 800M Controller / System 800xA
Product Type: Non-redundant AC 800M CPU module

ABB AC 800M 3BSE018168R1 PM851K01
Product Description
The PM851K01 3BSE018168R1 is an entry-level CPU module in the ABB AC 800M controller family. It is used for non-redundant process control applications and is engineered through Control Builder M under System 800xA.
The K01 variant is non-redundant. It provides two Ethernet ports for control network and engineering access, two RS-232C serial ports, ModuleBus for local S800 I/O, and a CEX-Bus slot for fieldbus communication modules.410
Technical Specifications
| Item | Description |
|---|---|
| Manufacturer | ABB |
| Model | PM851K01 |
| Order Code | 3BSE018168R1 |
| Product Family | AC 800M Controller |
| Redundancy | No |
| High Integrity / SIL | No |
| Memory | 12–16 MB RAM, depending on 800xA version |
| Performance | ~0.46 ms per 1000 boolean operations |
| Ethernet | 2 × 10/100Base-T RJ45 ports |
| Serial Ports | 2 × RS-232C (COM3 with modem signals; COM4 isolated for configuration) |
| Expansion | CEX-Bus for communication modules; ModuleBus for S800 I/O |
| Power Supply | 24 V DC nominal, typically 20–30 V DC |
| Power Consumption | Max. 7.2 W, typical 4.32 W |
| Operating Temperature | +5 to +55 °C |
| Storage Temperature | –40 to +70 °C |
| Protection | IP20 |
| Mounting | 35 mm DIN rail with TP830 baseplate |
| Dimensions / Weight | Approx. 119 × 135 mm; ~1.1 kg with baseplate |
Some specifications, especially memory size and firmware behavior, depend on the installed System 800xA version and hardware revision. For replacement, always verify the order code and revision against the unit label.310
Key Features
- Entry-level AC 800M CPU for non-redundant control nodes.
- Supports IEC 61131-3 programming via Control Builder M.
- Two Ethernet ports for control network and engineering access.
- Two RS-232C serial ports for configuration and external devices.
- CEX-Bus expansion for PROFIBUS DP, Modbus, FOUNDATION Fieldbus and other communication modules.
- ModuleBus interface for local S800 I/O connection.
- CompactFlash slot for application storage and firmware recovery.
- Low power consumption suitable for compact control cabinets.
Typical Applications
- Small to medium process control stations
- Utility and auxiliary control systems
- Water and wastewater treatment control
- HVAC and building automation control
- Packaging and material handling control systems
- Retrofit and lifecycle replacement for legacy AC 800M controllers
Related Products
- PM851AK01 3BSE066485R1: Updated PM851 variant.
- PM860AK01 / PM861AK01 / PM861AK02: Higher-performance AC 800M CPUs with redundancy support.
- PM864AK01 / PM864AK02: Faster AC 800M controllers for larger applications.
- PM866AK01 / PM866AK02: 64 MB AC 800M controllers.
- TP830: Baseplate used with PM851 CPU modules.
- CI85x / CI86x / CI87x: CEX-Bus communication modules for PROFIBUS DP, Modbus and other networks.