Description
1756-L73 Product Introduction
Overview
The 1756-L73 is an Allen‑Bradley (Rockwell Automation) ControlLogix Logix5573 controller, standard chassis CPU for normal ControlLogix racks (not K-keyed chassis). It has 8 MB user memory, supports sequential logic, closed-loop process regulation and CIP coordinated motion control, widely used for industrial automation, power auxiliary systems and production line master control. It is available as new original, surplus or refurbished spare.

1756-L73
Key Features & Benefits
- 8 MB user memory, 0.98 MB I/O memory, supports up to 32 tasks and max 128,000 I/O points
- Supports CIP Motion over EtherNet/IP, up to 32 coordinated motion axes
- No built-in Ethernet port; network realized by separate 1756-EN communication modules
- Front USB 2.0 port for program upload/download, online monitoring and fault diagnosis
- SD card slot for non-volatile program backup; 1756-ESMCAP supercap module for power-loss variable retention
- Supports hot-swap of ControlLogix I/O modules
- Programmed via Studio 5000 / RSLogix 5000 software
- LED indicators: RUN, FAULT, FORCE, BATTERY, SD status
- UL, CE, Class I Div.2 hazardous area certification
- Industrial shock & vibration specification, suitable for cabinet installation in power plant and heavy industry
| Item | Description |
|---|---|
| Manufacturer | Allen‑Bradley / Rockwell Automation |
| Model | 1756-L73 |
| Type | ControlLogix Logix5573 CPU Controller |
| User Memory | 8 MB |
| I/O Memory | 0.98 MB |
| Max Coordinated Motion Axes | 32 axes (CIP Motion) |
| Programming Port | USB 2.0 front port |
| Non-volatile Storage | SD card (sold separately) |
| Power Draw | 800mA @5.1VDC, 5mA @1.2VDC |
| Chassis Compatibility | Standard 1756-A4 / A7 / A10 / A13 chassis (NOT K-series AxxK chassis) |
| Software | Studio 5000 / RSLogix 5000 |
| Operating Temp | 0°C ~ +60°C |
| OEM Status | Mature active product |
| Application | Power auxiliary control, water treatment, packaging, metallurgy, process automation |
Typical Applications
1756-L73 acts as the main controller in standard ControlLogix racks, executing interlock logic, analog PID regulation, motor sequence control and drive motion control. It can connect with 2711P-T7C22D9P HMI for operator interface. It is a common spare for CPU overhaul and replacement during planned downtime.
Matching Companion Items
- Standard ControlLogix chassis 1756-A4 / A7 / A10
- Power supply 1756-PA75 / PB75
- 1756-EN2T / EN3TR EtherNet/IP communication module
- 1756 digital / analog I/O modules
- 1756-ESMCAP supercap retention module, SD memory card
- 2711P-T7C22D9P PanelView Plus 7 HMI
Operation Notes
1756-L73 is for standard A-series chassis, while 1756-L75K you listed before is K-keyed chassis version; they cannot be swapped directly. Confirm firmware revision and I/O configuration before replacement. Back up the controller project and verify all I/O and motion axes after commissioning.
FAQ
Q: What is the difference between 1756-L73 and 1756-L75? A: L73:8MB, max 32 motion axes; L75:32MB, max 100 motion axes. Q: What is the difference between 1756-L73 and 1756-L73XT? A: L73XT is extreme-temperature conformal coated version for wider temperature range. Q: Can it communicate with Honeywell Experion or DeltaV? A: Yes via Modbus TCP / OPC UA gateway; it is not native DCS module.