T8111C | ICS Triplex (Rockwell Automation) Trusted TMR Safety Processor
Brand Label
Brand: ICS Triplex (Acquired by Rockwell Automation) Part No.: T8111C Product Name: Trusted Triple Modular Redundant (TMR) Safety Processor Module Series: Trusted TMR SIS System Origin: UK Compliance: IEC 61508 SIL3, TÜV certified, ATEX / IECEx Zone 2, CE Status: Obsolete / End-of-Life, high-demand critical spare for legacy ESD/FGS/BMS systems Function: Core lock-step TMR safety controller, executes safety logic, I/O voting, diagnostics and host communication for safety instrumented systems
Technical Specifications
| Item | Parameter |
|---|---|
| Architecture | Triple Modular Redundant (TMR), lock-step voting |
| Safety Rating | IEC 61508 SIL 3 |
| Front Port | RS232 diagnostic serial port for commissioning & troubleshooting |
| Synchronization | IRIG-B002 / IRIG-B122 time sync for SOE sequence of events |
| Serial Interfaces | 2 × configurable RS422/485 (2/4 wire) + 1 × RS485 2-wire |
| Relay Outputs | Active / standby status & fault alarm dry contacts |
| Backplane Bus | Trusted Safetybus for connection to Trusted I/O modules |
| Operating Temperature | -40 °C ~ +70 °C |
| Mounting | Trusted standard rack slot mount |
| Software | Trusted Toolset Suite (IEC 61131 programming) |
| Application | Oil & gas, refinery, chemical, power plant ESD emergency shutdown, fire & gas, burner management, turbine safety interlocks |
Key Features & Advantages
- Three independent processors run identical logic with majority voting; continues operation with one processor fault
- Comprehensive continuous self‑diagnosis for CPU, memory, bus, voter circuit and internal power rails
- Built‑in IRIG‑B time synchronization for accurate sequence‑of‑events (SOE) fault logging
- Front panel key switch for maintenance mode, local status LED indicators for fast troubleshooting
- Supports simplex, dual redundant hot‑standby processor configuration for maximum availability
- Seamless interoperability with full Trusted TMR I/O portfolio (DI, DO, AI, AO)
- Proven long-term field deployment, widely paired with HIMA, VM600, Mark VIe turbine safety packages
- TÜV SIL3 safety certification traceable for plant safety audit documentation
Recommended 6 Related / Alternative Models
- T8110B – Earlier Trusted TMR processor predecessor
- T8151C – Trusted communication interface module (Ethernet/Modbus gateway)
- T8403C – 24-channel digital input module for Trusted rack
- T8461C – 16-channel safety digital output module
- T8311C – 20-channel isolated analog input 4–20 mA module
- AADvance T9100 – Rockwell modern SIL3 TMR safety controller for new greenfield SIS
Brand & Trusted TMR Platform Brief History
ICS Triplex, founded in the UK, was one of the pioneers of TMR safety technology for process SIS, later acquired by Rockwell Automation under its safety portfolio.
The Trusted TMR platform was developed as a rack-based high-integrity safety system built around lock-step triple redundant architecture. T8111C is one of the later generation core processor cards for this family. It receives signals from the Trusted I/O backplane, executes safety logic, performs fault voting and communicates status to DCS/SCADA hosts.
Rockwell ended new production of the legacy Trusted T8111C hardware, directing new safety projects to the AADvance platform. Even so, T8111C remains a top priority spare for the large global installed fleet of ESD and FGS cabinets in refineries, offshore platforms and power stations.
FAQ
- Can T8111C run standalone without Trusted I/O modules? No, it relies on the Trusted Safetybus backplane to connect with I/O modules for field signal acquisition and output control.
- What is the difference between T8110B and ? is a revised upgraded variant with improved diagnostics and IRIG-B timing features; verify firmware compatibility before replacement.
- Can AADvance T9100 drop-in replace Trusted ? Not drop-in compatible; different rack, backplane, engineering software and I/O family, requires full SIS re-engineering.