660-10100 | Omniguard (Firefly / Vibro-Meter / Meggitt) Single Spectrum UV Flame Detector
Brand Label
Brand: Omniguard (Firefly, supplied within Vibro‑Meter / Meggitt turbine safety package) Part No.: 660-10100 Product Name: UV Flame Detector Series: Omniguard 660 Series Origin: USA Compliance: ATEX, IECEx, FM, CSA, SIL 2 capable, CE Status: Legacy flame detector, high-demand spare for gas turbine enclosure FGS Function: Ultraviolet flame detection for hydrocarbon and hydrogen flames, relay alarm and fault output for fire & gas safety loops
Technical Specifications
| Item | Parameter |
|---|---|
| Detection Principle | Single-spectrum UV sensor (ultraviolet photocell) |
| Field of View | 120° wide angle |
| Response Time | ≤15 ms for saturated flame; ~1 s for 1 sq. ft gasoline flame @ 50 ft |
| Detectable Fuels | Hydrocarbon, hydrogen, silane, magnesium |
| Supply | 24 V DC nominal |
| Output | Alarm relay, fault relay; selectable latching / non-latching |
| Self-test | Through-lens automatic optical and electronic self-diagnosis |
| Operating Temperature | -40 °C ~ +85 °C (standard) |
| Enclosure | Explosion-proof; IP66 / IP67 |
| Mounting | Surface mount for turbine enclosure, compressor skid, hazardous zone |
| Application | Gas turbine packages, LNG/LPG facilities, hydrogen test cells, FGS integrated with VM600, Mark VIe, HIMA SIS |
Key Features & Advantages
- Ultra-fast UV detection, excellent sensitivity to nearly invisible hydrogen flames
- 120° wide viewing angle reduces required detector quantity per protected zone
- Continuous self-check for window fouling, UV tube failure and internal circuit faults
- Explosion-proof housing certified for Zone 1 hazardous locations
- Relay dry contacts are easy to interface with legacy safety I/O racks
- Long field-proven track record, commonly bundled with Vibro-Meter turbine monitoring systems
- Simple wiring and adjustable sensitivity/delay to filter nuisance alarms
Recommended 6 Related / Alternative Models
- 660-10200 – High-temperature 125 °C UV version
- 760-10100 – Omniguard single IR flame detector, better sunlight immunity
- 860-10100 – Omniguard UV/IR dual-spectrum detector, lower false alarm rate
- FS20X – Firefly modern multi-spectrum SIL2 flame detector
- SS4 – Spectrex UV/IR flame detector, cross-brand common replacement
- 204-070-000-001 – VM600 AMC16 analog input card for flame signal integration
Brand & Platform Brief History
Omniguard flame detectors belong to Firefly, and Vibro‑Meter (Meggitt) integrated this model into its turbine safety and fire & gas packages, paired with VM600 machinery protection systems for power and oil & gas sites.
The 660 series is a classic single UV design. Its main strength is speed and hydrogen flame response; the trade-off is higher susceptibility to UV interference such as welding arcs and lightning compared to dual-spectrum UV/IR models.
New greenfield projects usually select 860 series or newer multi-spectrum detectors. The 660-10100 remains an important spare for the large installed base of gas turbine FGS systems globally.