T9110 Product Introduction

  • T9100 processor base / power base
  • AADvance I/O modules: T9401 DI, T9402 DO, T9431 AI, T9451 AO
  • T98xx series terminal assemblies
  • AADvance Workbench configuration software
  • SIS isolation barriers, field transmitters and trip solenoids

 

Category: SKU: T9110 Brand:

Description

T9110 Product Introduction

 

Overview

The T9110 is the AADvance safety processor module of ICS Triplex (Rockwell / Allen‑Bradley) SIS safety instrumented system. It executes safety control logic, interlock protection and fault diagnosis for SIL3 safety-critical applications, widely used in power plant boiler/turbine, refinery and chemical emergency trip systems. It supports single, dual and TMR triple redundant configurations and is available as new original, surplus or refurbished spare.

T9110

Key Features & Benefits

  • IEC 61508 SIL3 certified safety processor, independent watchdog and comprehensive self-diagnosis
  • 2 × Ethernet ports + 2 × RS485 serial ports; supports Modbus RTU/TCP, IEC 61131-3 programming
  • Battery-backed RTC and retention memory for alarm event timestamps and retained variables
  • Hot-swappable design for online replacement without system shutdown
  • Built-in fault detection: CPU fault, bus fault, I/O channel fault, communication timeout
  • Works with AADvance I/O modules (T9401, T9402, T9431, T9451, T9481 etc.)
  • Supports TMR triple modular redundancy for turbine/boiler fuel trip, ESD protection
  • Conformal-coated PCB, anti-vibration, suitable for noisy control cabinet environments
  • MTBF: 45.72 years, high safety reliability for continuous process operation

 

Technical Specifications

Item Description
Manufacturer ICS Triplex / Rockwell Automation
Model T9110
Type AADvance SIS Safety Processor Module
Safety Level SIL3 (TMR), SIL2 (simplex)
Power Supply 18–32 VDC
Communication 2 × Ethernet, 2 × RS485
Engineering Software AADvance Workbench
Mounting DIN rail AADvance rack, paired with T9100 base
Protection Class IP20
Operating Temperature -20°C ~ +60°C
OEM Status Mature safety product, spare support available
Application ESD, burner trip, boiler / gas turbine SIS, chemical process safety interlock

 

Typical Applications

T9110 is deployed in AADvance SIS racks for combined-cycle power plants and refineries. It executes emergency shutdown, flame loss trip, lube oil permissive, over-speed protection and safety interlock logic. It is a high-demand safety spare for unit overhaul and SIS rack maintenance.

 

Matching Companion Items

  • T9100 processor base / power base
  • AADvance I/O modules: T9401 DI, T9402 DO, T9431 AI, T9451 AO
  • T98xx series terminal assemblies
  • AADvance Workbench configuration software
  • SIS isolation barriers, field transmitters and trip solenoids

 

Operation Notes

T9110 must be installed on T9100 base. Hardware revision and firmware version must match the whole SIS rack before replacement. After swapping, full SIS logic proof test and SIL function verification are mandatory. Different revision variants are not always drop-in compatible.

 

FAQ

Q: Can T9110 run independently? A: No, it must be installed with T9100 base and paired AADvance I/O modules. Q: Can it communicate with Honeywell Experion or DeltaV? A: Yes via Modbus TCP; it is an independent SIS controller, not native DCS card. Q: What is the difference between and T9120? A: Both are AADvance processors, different performance and memory capacity; project validation required for replacement.